Bryant 551B, 558F, 551A manual MODEL NUMBER NOMENCLATURE - 559F, 5 5 9 F E X 1 8 0 0 0 0 A H C B

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 109
Image 109

MODEL NUMBER NOMENCLATURE — 559F

5 5 9 F E X 1 8 0 0 0 0 A H C B

559F – Standard Efficiency

Electric Cooling Unit

Voltage Designation

E 460-3-60

P 208/230-3-60

Heat Type

X – No Heat Installed

(Field-installed electric heaters available)

Nominal Tons 180 – 15 216 – 18 240 – 20 300 – 25

Electric Heaters

000 – No factory-installed electric heaters

Fan Drive Position

(Standard Motor)

B– Standard Low-Medium Fan Drive Static Capability

D– Alternate High Fan Drive Static Capability

Factory-Installed

Outdoor Air and Other

Upgrade Options

C – EconoMi$er

H– Manual Outdoor-Air Damper

Design Series Code

AH – Original Design Series

NOTE: The example model number 559FEX180000AHCB designates a 15-ton 460-3-60 volt electric cooling rooftop unit with scroll compressors, TXVs, EconoMi$er and the standard low-medium fan drive static capability.

 

 

 

ARI* CAPACITY RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

559F180

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOMINAL

STANDARD

 

NET COOLING

TOTAL

 

SOUND

 

 

CAPACITY

EER

RATING

IPLV

 

 

 

559F

TONS

CFM

 

WATTS

 

 

 

 

(Btuh)

 

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

180

15

5250

 

176,000

19,813

8.9

88

9.6

 

 

 

216

18

6200

 

188,000

21,298

8.8

88

9.8

 

-300

 

240

20

6600

 

220,000

25,146

8.7

95

8.9

 

 

300

25

7200

 

268,000

30,858

8.7

95

9.3

 

 

 

 

 

LEGEND

dB

Sound Levels (decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio

IPLV

Integrated Part-Load Values

wb

Wet Bulb

*Air Conditioning and Refrigeration Institute.

NOTES:

1.Rated in accordance with ARI Standards 360-89 and 270-89.

2.The 559F300 is beyond the scope of the ARI Certification Program.

3.ARI ratings are net values, reflecting the effects of circulating fan heat.

4.Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db air entering outdoor unit.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

5.These units do not comply with ASHRAE 90.1-1999 efficiency requirements.

AIR QUANTITY LIMITS

UNIT 559F

MINIMUM CFM

MAXIMUM CFM

180

4500

7,500

216

5400

9,000

240

6000

10,000

300

7000

11,250

LOW OUTDOOR TEMPERATURE

OPERATING LIMITS (F)

UNITS

TEMPERATURE

All

40

180 and 216 with Low Ambient Kit

10

240 and 300 with Low Ambient Kit

25

All with Head Pressure Control

–20

109

Page 109
Image 109
Bryant 551B MODEL NUMBER NOMENCLATURE - 559F, 5 5 9 F E X 1 8 0 0 0 0 A H C B, Air Quantity Limits, Ari* Capacity Ratings