Bryant 551A Outdoor Sound Power, ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F180, 559F180-300

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 125
Image 125

PERFORMANCE DATA (cont)

OUTDOOR SOUND POWER

UNIT

SOUND

A-WEIGHTED

 

 

 

OCTAVE BANDS

 

 

 

559F

RATING dB

(dB)

63

125

250

500

1000

2000

4000

8000

(60 Hz)

 

 

 

 

 

 

 

 

 

 

180

88

87.8

90.8

88.7

86.4

84.3

83.5

78.4

75.6

66.8

216

88

87.8

90.8

88.7

86.4

84.3

83.5

78.4

75.6

66.8

240

95

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

300

95

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

LEGEND

Bels — Sound Levels (1 bel = 10 decibels)

ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 559F180

COMPONENT

 

 

CFM

 

 

4500

5000

6000

7200

7500

 

EconoMi$er

0.04

0.05

0.07

0.09

0.10

Glycol Coil

0.22

0.26

0.35

0.44

0.46

Electric Heat (kW)

 

 

 

 

 

26/34

0.06

0.07

0.09

0.11

0.12

32

0.06

0.07

0.09

0.11

0.12

42/56

0.07

0.08

0.12

0.16

0.17

50

0.09

0.10

0.15

0.20

0.21

55

0.07

0.08

0.12

0.15

0.17

56/75

0.09

0.10

0.15

0.20

0.21

80

0.09

0.10

0.15

0.20

0.21

Perfect Humidity™ Dehumidification Package

0.05

0.05

0.07

0.10

0.11

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 559F216-300

COMPONENT

 

 

 

CFM

 

 

5400

6000

7200

9000

10,000

11,250

 

EconoMi$er

0.06

0.07

0.09

0.11

0.12

0.14

Glycol Coil

0.30

0.35

0.44

0.58

0.66

0.77

Electric Heat (kW)

 

 

 

 

 

 

26/34

0.08

0.09

0.11

0.15

0.17

0.20

32

0.08

0.09

0.11

0.15

0.17

0.20

42/56

0.11

0.12

0.15

0.19

0.21

0.24

55

0.11

0.12

0.15

0.19

0.21

0.24

56/75

0.14

0.15

0.20

0.24

0.26

0.29

80

0.14

0.15

0.20

0.24

0.26

0.29

Perfect Humidity Dehumidification Package

0.06

0.07

0.10

0.16

0.20

0.25

LEGEND

 

 

 

 

 

 

FIOP — Factory-Installed Option

 

 

 

 

 

 

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS*

UNIT 559F

 

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

0

1/

2

1

11/

2

 

21/

3

31/

 

4

41/

5

51/

6

 

 

 

 

 

 

 

2

 

 

2

 

2

 

 

2

 

2

 

180†

††

††

1179

1150

1121

 

1093

1064

1035

 

1006

978

949

920

891

180**

††

††

1559

1522

1488

 

1455

1422

1389

 

1356

1323

1289

1256

1227

216†

††

††

1095

1077

1058

 

1040

1021

1002

 

984

965

947

928

910

216**

††

††

1287

1265

1243

 

1222

1200

1178

 

1156

1134

1112

1091

1069

240†

††

††

1225

1209

1187

 

1165

1143

1120

 

1098

1076

1053

1031

1002

240**

††

††

1458

1434

1407

 

1381

1354

1328

 

1301

1275

1248

1222

1193

300†

††

††

1283

1269

1247

 

1225

1203

1182

 

1160

1138

1116

1095

1066

300**

††

††

1551

 

1524

1497

1470

 

1443

1415

1388

1361

1332

*Approximate fan rpm shown.

†Indicates standard drive package. **Indicates alternate drive package.

††Due to belt and pulley size, pulley cannot be set to this number of turns open.

559F180-300

125

Page 125
Image 125
Bryant 551A Outdoor Sound Power, ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F180, PERFORMANCE DATA cont, 559F180-300