PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

551A155 (13 TONS) UNITS WITH PERFECT HUMIDITY™ OPTION

Temp (F)

 

 

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

Air Entering

 

3600/0.03

 

 

 

 

4375/0.04

 

 

 

5000/0.05045

 

 

5625/0.06

 

 

 

6250/0.07

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

67

 

72

 

 

62

 

67

72

 

62

 

67

72

 

62

 

67

72

 

62

 

67

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

139

 

153

 

130

 

144

153

 

135

 

145

155

 

138

 

147

159

 

145

 

149

156

 

SHC

 

81

 

63

 

111

 

93

68

 

118

 

98

68

 

125

 

104

72

 

135

 

109

72

 

 

kW

 

8.0

 

8.2

 

7.9

 

8.3

8.2

 

7.9

 

8.1

8.3

 

8.0

 

8.2

8.3

 

8.3

 

8.2

8.3

85

 

TC

 

133

 

142

 

125

 

137

146

 

129

 

138

146

 

132

 

140

148

 

135

 

142

148

 

SHC

 

75

 

56

 

105

 

84

61

 

113

 

93

62

 

120

 

98

66

 

125

 

100

67

 

 

kW

 

8.9

 

9.1

 

8.8

 

9.2

9.2

 

8.8

 

9.0

9.0

 

8.8

 

9.0

9.2

 

9.1

 

9.1

9.3

95

 

TC

 

126

 

135

 

119

 

129

137

 

123

 

132

139

 

125

 

133

139

 

128

 

135

139

 

SHC

 

70

 

52

 

99

 

78

56

 

106

 

84

59

 

112

 

90

60

 

117

 

95

61

 

 

kW

 

9.9

 

10.1

 

9.7

 

9.9

10.1

 

9.9

 

10.0

10.2

 

9.9

 

10.1

10.1

 

9.9

 

10.1

10.1

105

 

TC

105

 

119

 

127

 

110

 

122

130

 

113

 

124

130

 

115

 

125

131

 

118

 

126

132

 

SHC

80

 

65

 

47

 

92

 

73

51

 

97

 

78

52

 

104

 

83

55

 

108

 

89

57

 

 

kW

10.6

 

10.9

 

11.1

 

10.8

 

11.0

11.2

 

10.9

 

11.0

11.1

 

10.8

 

11.0

11.2

 

10.9

 

11.1

11.3

115

 

TC

90

 

108

 

119

 

97

 

112

121

 

97

 

115

122

 

100

 

116

123

 

106

 

118

123

 

SHC

66

 

57

 

41

 

79

 

66

45

 

80

 

72

47

 

88

 

76

49

 

95

 

80

51

 

 

kW

11.7

 

12.1

 

12.3

 

11.8

 

12.2

12.4

 

11.8

 

12.3

12.5

 

12.0

 

12.4

12.5

 

12.1

 

12.3

12.5

117

 

TC

86

 

100

 

111

 

98

 

112

121

 

99

 

114

121

 

102

 

116

123

 

107

 

117

123

 

SHC

64

 

52

 

38

 

63

 

58

45

 

67

 

61

47

 

72

 

63

48

 

77

 

66

50

 

 

kW

12.8

 

13.2

 

13.6

 

12.0

 

12.3

12.5

 

12.0

 

12.3

12.5

 

11.9

 

12.4

12.5

 

12.1

 

12.4

12.5

120

 

TC

90

 

102

 

114

 

90

 

107

117

 

91

 

109

118

 

93

 

111

119

 

99

 

113

119

 

SHC

67

 

52

 

38

 

71

 

61

41

 

76

 

66

44

 

81

 

70

46

 

87

 

75

47

 

 

kW

12.3

 

12.6

 

12.8

 

12.3

 

12.7

12.9

 

12.3

 

12.8

12.9

 

12.3

 

12.8

13.0

 

12.5

 

12.9

13.0

125

 

TC

83

 

95

 

109

 

85

 

97

112

 

87

 

103

113

 

88

 

105

114

 

90

 

107

114

 

SHC

61

 

47

 

35

 

66

 

53

38

 

72

 

61

41

 

76

 

66

44

 

78

 

70

45

 

 

kW

12.8

 

13.1

 

13.5

 

12.8

 

13.1

13.5

 

12.9

 

13.3

13.5

 

12.8

 

13.4

13.6

 

12.9

 

13.4

13.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

551A180 (15 TONS) UNITS WITH PERFECT HUMIDITY OPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

Air Entering

 

 

4500/0.02

 

 

 

5250/0.03

 

 

6000/0.03905

 

 

 

6750/0.04

 

 

 

7500/0.05

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

62

67

72

 

62

67

72

 

 

 

 

 

 

 

 

75

 

TC

185

203

 

175

191

209

 

179

195

212

 

182

198

213

 

186

200

216

 

SHC

105

82

 

141

115

88

 

154

125

96

 

165

135

104

 

174

145

109

 

 

kW

11.3

11.7

 

11.0

11.4

11.8

 

11.1

11.5

11.9

 

11.2

11.6

11.9

 

11.3

11.7

12.0

85

 

TC

176

193

 

166

183

199

 

170

186

202

 

173

189

204

 

177

190

205

 

SHC

98

74

 

134

108

81

 

145

116

85

 

156

126

93

 

162

134

97

 

 

kW

12.3

12.7

 

12.1

12.9

13.4

 

12.1

12.6

13.5

 

12.2

12.7

13.5

 

12.7

12.2

12.7

95

 

TC

168

182

 

156

173

187

 

160

176

191

 

163

178

194

 

167

181

196

 

SHC

91

66

 

126

100

72

 

137

108

76

 

146

116

82

 

153

125

86

 

 

kW

13.7

13.5

 

13.1

13.6

13.9

 

13.2

13.6

14.1

 

13.3

13.4

14.3

 

13.5

13.9

14.6

105

 

TC

156

173

 

145

160

175

 

148

162

177

 

151

166

178

 

154

167

180

 

SHC

83

59

 

117

90

62

 

127

98

66

 

136

106

70

 

141

112

74

 

 

kW

14.5

15.3

 

14.2

14.8

15.1

 

14.4

14.5

15.1

 

14.4

14.9

14.9

 

14.2

14.6

14.9

115

 

TC

141

156

 

130

146

160

 

132

150

162

 

135

150

164

 

139

152

166

 

SHC

72

47

 

104

79

52

 

112

86

55

 

119

93

59

 

127

100

63

 

 

kW

15.6

15.9

 

15.2

15.8

16.2

 

15.3

16.1

16.3

 

15.4

16.0

16.4

 

15.8

16.1

16.4

118

 

TC

138

151

 

126

141

153

 

129

144

134

145

135

148

 

SHC

68

43

 

100

74

46

 

108

83

120

88

124

96

 

 

kW

16.1

16.5

 

15.7

16.1

16.5

 

15.8

16.3

16.0

16.3

15.9

16.3

120

 

TC

134

 

124

 

126

 

 

 

 

SHC

65

 

99

 

106

 

 

 

 

 

kW

16.2

 

15.9

 

16.0

 

 

 

125

 

TC

— —

 

 

 

 

 

 

 

SHC

 

 

 

 

 

 

 

 

kW

— —

 

 

 

 

 

 

551A155

LEGEND

BF — Bypass Factor Edb — Entering Dry-BulbEwb — Entering Wet-Bulb

kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb

lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb = tedb

sensible capacity (Btuh)

1.10 x cfm

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

 

76

75

 

under 75
FACTOR

 

 

81

82

83

 

84

85

 

over 85

(BF)

 

 

 

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

 

4.14

5.18

 

Use formula

.10

.98

1.96

2.94

 

3.92

4.90

 

.20

.87

1.74

2.62

 

3.49

4.36

 

shown below.

.30

.76

1.53

2.29

 

3.05

3.82

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

-180

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo- rator coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

159