Bryant 551A PERFORMANCE DATA cont, COOLING CAPACITIES cont, 559F180, tldb, tlwb =, hlwb =, hewb

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 122
Image 122

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

 

 

 

559F240 (20 TONS) — UNITS WITH PERFECT HUMIDITY™ OPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

 

Air Entering

 

6,000/0.07

 

 

7,000/0.09

 

 

 

8,000/0.1

 

 

 

9,000/0.11

 

 

10,000/0.12

 

 

 

 

Condenser

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

67

72

62

67

72

 

62

67

72

 

62

67

72

62

67

72

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

237

261

249

269

 

254

274

 

252

279

230

255

283

 

 

 

75

 

SHC

141

111

155

118

 

166

125

 

175

132

228

186

139

 

 

 

 

 

kW

16.2

16.9

17.3

17.1

 

17.2

17.3

 

16.7

17.5

16.3

16.9

17.6

 

 

 

 

 

TC

227

251

233

257

 

238

263

 

241

267

220

243

269

 

 

 

85

 

SHC

133

103

145

110

 

157

117

 

166

123

220

177

129

 

 

 

 

 

kW

17.5

18.2

17.8

18.3

 

18.0

18.5

 

18.6

18.7

17.4

17.7

18.3

 

 

 

 

 

TC

215

238

221

246

 

224

249

 

207

228

254

211

231

256

 

 

 

95

 

SHC

125

94

136

102

 

147

108

 

199

158

114

210

167

120

 

 

 

 

 

kW

18.7

19.0

18.8

19.6

 

18.6

19.6

 

18.6

19.3

19.9

19.1

19.4

20.1

 

 

 

 

 

TC

205

227

208

230

 

214

237

 

195

213

241

198

217

241

 

 

 

105

 

SHC

117

86

128

92

 

138

99

 

188

147

104

198

156

110

 

 

 

 

 

kW

20.2

20.9

20.0

20.3

 

20.7

21.3

 

19.8

19.9

21.2

19.9

20.6

20.9

 

 

 

 

 

TC

190

211

195

217

 

197

219

 

183

203

222

186

204

227

 

 

 

115

 

SHC

108

77

119

82

 

127

88

 

176

138

94

186

147

99

 

 

 

 

 

kW

21.2

22.1

21.6

22.2

 

21.2

22.1

 

21.1

22.1

22.1

21.3

21.9

22.6

 

 

 

 

 

TC

176

196

179

198

 

183

204

 

169

183

207

172

185

207

 

 

 

125

 

SHC

97

65

107

70

 

116

76

 

165

124

81

172

133

86

 

 

 

 

 

kW

22.8

23.4

22.8

22.9

 

23.0

23.7

 

22.5

22.8

24.1

22.7

22.9

23.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

559F300 (25 TONS) — UNITS WITH PERFECT HUMIDITY OPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

 

Air Entering

 

7,000/0.05

 

 

8,000/0.06

 

 

 

9,000/0.07

 

 

 

10,000/0.08

 

 

11,250/0.09

 

 

 

 

Condenser

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

67

72

62

67

72

 

62

67

72

 

62

67

72

62

67

72

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

287

325

301

332

 

300

331

 

272

299

336

278

304

341

 

 

 

75

 

SHC

175

139

191

148

 

204

156

 

259

214

163

276

228

177

 

 

 

 

 

kW

20.6

22.4

21.7

22.7

 

21.0

22.0

 

19.7

20.4

22.2

19.9

20.6

22.4

 

 

 

 

 

TC

268

298

277

306

 

281

312

 

259

286

317

265

289

321

 

 

 

85

 

SHC

161

123

173

130

 

186

138

 

244

197

145

262

213

157

 

 

 

 

 

kW

21.5

22.4

22.0

22.7

 

22.0

22.9

 

21.1

22.2

23.1

21.7

22.1

23.3

 

 

 

 

 

TC

253

286

261

290

 

269

296

 

244

271

301

250

275

307

 

 

 

95

 

SHC

149

111

161

117

 

173

124

 

231

184

131

246

199

140

300-

 

 

 

kW

23.1

24.9

23.6

24.5

 

24.2

24.9

 

23.1

24.2

25.2

23.4

24.5

25.4

 

 

 

TC

240

266

247

273

 

249

277

 

229

254

280

234

256

285

 

 

 

 

 

 

 

 

 

 

105

 

SHC

136

97

148

103

 

158

111

 

217

169

115

231

182

122

 

 

 

 

 

kW

25.1

26.0

25.6

26.6

 

25.3

26.5

 

25.0

25.7

26.5

25.1

25.7

26.7

 

559F180

 

115

 

TC

222

248

228

253

 

210

232

257

 

213

233

263

215

239

265

 

 

 

TC

 

 

 

 

 

 

SHC

122

82

133

88

 

188

144

94

 

201

153

100

212

166

107

 

 

 

 

 

kW

26.8

27.8

27.0

28.1

 

26.6

27.4

28.1

 

26.7

27.3

28.8

26.7

27.9

28.7

 

 

 

 

 

TC

212

218

 

197

221

 

201

224

203

225

 

 

 

121

 

SHC

113

124

 

177

134

 

190

143

201

156

 

 

 

 

 

kW

28.2

28.5

 

27.7

28.6

 

27.9

28.9

28.0

28.9

 

 

 

125

 

SHC

 

 

 

 

 

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

BF — Bypass Factor Edb — Entering Dry-BulbEwb — Entering Wet-Bulb

kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb

lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity (Btuh)

tldb

= tedb

 

1.10 x cfm

 

 

 

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

ENTERING AIR DRY-BULB TEMP (F)

BYPASS FACTOR

79

78

77

76

75

under 75

(BF)

81

82

83

84

85

over 85

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

.10

.98

1.96

2.94

3.92

4.90

Use formula

.20

.87

1.74

2.62

3.49

4.36

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

tlwb =

Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (hlwb)

hlwb =
hewb

total capacity (Btuh)

 

4.5 x cfm

 

 

Where: hewb = Enthalpy of air entering evaporator coil

GENERAL FAN PERFORMANCE NOTES

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See page 125 for accessory/factory-installed option static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in

nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance table on page 126 for additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.

4.Interpolation is permissible. Do not extrapolate.

122