Bryant 551B, 558F manual FAN PERFORMANCE - 551A155,180 UNITS, PERFORMANCE DATA cont

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 160
Image 160

PERFORMANCE DATA (cont)

GLYCOL HEATING PERFORMANCE

GLYCOL COIL (551A155,180)

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Cfm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5400

 

 

 

 

 

 

 

7200

 

 

 

 

 

Entering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Percent Glycol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

25

 

 

 

 

50

 

 

 

 

25

 

 

 

50

 

 

Edb

 

Ewt

Cap

Gpm

Ldb

 

Cap

 

Gpm

 

 

 

Ldb

 

Cap

 

Gpm

Ldb

 

Cap

Gpm

Ldb

 

Cap

 

Gpm

Ldb

Cap

 

Gpm

 

Ldb

 

 

200

 

310

 

33

 

120

 

 

293

 

33

 

 

 

116

 

 

347

 

37

115

 

327

37

111

 

405

 

43

107

381

 

43

 

104

55

 

180

 

255

 

27

 

108

 

 

237

 

27

 

 

 

105

 

 

285

 

30

104

 

264

30

101

 

332

 

35

98

306

 

35

 

95

 

 

160

 

200

 

21

 

97

 

 

181

 

21

 

 

 

93

 

 

223

 

24

94

 

202

23

90

 

259

 

27

89

233

 

27

 

85

 

 

200

 

274

 

29

 

127

 

 

257

 

29

 

 

 

124

 

 

306

 

32

123

 

287

33

119

 

357

 

38

116

333

 

38

 

113

70

 

180

 

218

 

23

 

116

 

 

201

 

23

 

 

 

112

 

 

244

 

26

112

 

224

26

109

 

284

 

30

107

259

 

30

 

104

 

 

160

 

164

 

17

 

104

 

 

146

 

17

 

 

 

100

 

 

183

 

19

101

 

162

19

98

 

212

 

22

97

187

 

22

 

94

 

 

200

 

249

 

26

 

132

 

 

233

 

27

 

 

 

129

 

 

279

 

30

128

 

260

30

125

 

325

 

34

122

302

 

34

 

119

80

 

180

 

194

 

21

 

121

 

 

177

 

20

 

 

 

117

 

 

217

 

23

117

 

197

23

114

 

252

 

26

113

228

 

27

 

109

 

 

160

 

140

 

15

 

109

 

 

123

 

14

 

 

 

106

 

 

156

 

16

107

 

136

16

103

 

180

 

18

103

156

 

19

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLYCOL COIL (551A155,180) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

 

Air Entering Evaporator — Cfm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

9000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

25

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Edb

 

Ewt

 

Cap

 

Gpm

 

Ldb

 

 

Cap

 

Gpm

 

 

Ldb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

453

 

48

 

102

 

 

 

425

 

48

 

 

 

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

180

 

371

 

39

 

93

 

 

 

342

 

39

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

 

290

 

31

 

85

 

 

 

260

 

30

 

 

 

82

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

400

 

42

 

111

 

 

 

372

 

42

 

 

 

108

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

180

 

317

 

34

 

103

 

 

 

287

 

33

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

 

237

 

25

 

94

 

 

 

208

 

24

 

 

 

91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

364

 

39

 

118

 

 

 

337

 

38

 

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

180

 

281

 

30

 

109

 

 

 

254

 

29

 

 

 

106

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

 

201

 

21

 

101

 

 

 

173

 

20

 

 

 

78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLYCOL COIL RATINGS (551A155,180)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluid

 

 

 

 

4,000

 

 

 

 

 

 

 

 

 

5,000

 

 

 

 

 

6,000

 

 

8,000

 

 

 

 

10,000

 

 

 

Temp (F)

 

 

Gpm

 

 

 

 

P*

 

 

Gpm

 

P*

 

 

Gpm

 

P*

 

Gpm

 

P*

 

 

Gpm

 

 

 

P*

 

200

 

 

 

27

 

 

 

 

 

1.2

 

 

 

31

 

 

 

1.5

 

 

35

 

 

 

1.8

 

41

 

2.4

 

 

47

 

 

 

2.9

 

180

 

 

 

22

 

 

 

 

 

0.9

 

 

 

25

 

 

 

1.1

 

 

27

 

 

 

1.3

 

32

 

1.6

 

 

36

 

 

 

2.0

 

160

 

 

 

16

 

 

 

 

 

0.6

 

 

 

19

 

 

 

0.7

 

 

20

 

 

 

0.8

 

24

 

1.0

 

 

27

 

 

 

1.2

 

LEGEND

Cap

Btuh × 1000

Edb

Entering Dry Bulb Temperature (F)

Ewt

Entering Water Temperature (F)

Gpm

Gallons Per Minute

Ldb

Leaving Dry-Bulb Temperature (F)

*P is the fluid pressure in ft of head.

NOTES:

1.This accessory glycol coil is intended for use with a MINIMUM of 25% glycol solution. It IS NOT intended for use solely with water due to freeze-up conditions and the resulting water damage to the conditioned space.

2.Water = 20 F.

FAN PERFORMANCE — 551A155,180 UNITS

 

 

 

551A155 WITH STANDARD MOTOR*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

Cfm

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

 

 

 

3750

753

915

1.05

786

972

1.12

892

1170

1.35

991

1378

1.58

1084

1595

1.83

 

 

 

4000

747

977

1.12

810

1090

1.25

911

1292

1.49

1007

1503

1.73

1097

1723

1.98

 

 

 

4250

741

1041

1.20

835

1220

1.40

932

1426

1.64

1024

1640

1.89

1111

1863

2.14

 

 

 

4500

761

1158

1.33

861

1360

1.56

954

1570

1.81

1043

1788

2.06

1127

2014

2.32

 

 

 

4750

792

1305

1.50

887

1512

1.74

977

1726

1.99

1063

1948

2.24

1145

2177

2.50

 

 

 

5000

823

1464

1.68

915

1676

1.93

1002

1894

2.18

1084

2120

2.44

1164

2352

2.70

 

 

 

5250

855

1635

1.88

943

1852

2.13

1027

2075

2.39

1107

2304

2.65

1184

2539

2.92

 

 

 

5500

887

1819

2.09

972

2041

2.35

1053

2268

2.61

1130

2501

2.88

 

 

 

5750

920

2016

2.32

1002

2242

2.58

1079

2473

2.84

180-

 

6000

953

2226

2.56

1031

2457

2.83

1107

2692

3.10

 

6250

986

2449

2.82

1062

2685

3.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

551A155

 

551A155 WITH STANDARD MOTOR* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

 

 

 

3750

1172

1822

2.10

1256

2057

2.37

1337

2299

2.64

1414

2549

2.93

 

 

 

4000

1182

1952

2.24

1264

2188

2.52

1343

2432

2.80

1418

2683

3.09

 

 

 

4250

1194

2093

2.41

1274

2332

2.68

1351

2577

2.96

 

 

 

4500

1208

2247

2.58

1286

2487

2.86

 

 

 

4750

1223

2412

2.77

1299

2655

3.05

 

 

 

5000

1240

2590

2.98

 

 

 

5250

 

 

 

5500

 

 

 

5750

 

 

 

6000

 

 

 

6250

LEGEND

Bhp — Brake Horsepower

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Standard low-medium static drive range is 834 to 1064 rpm (for 208/230 and 460-v units). Alternate high-static drive range is 1161 to 1426 (for 208/230 and 460-v units). Other rpms require a field-supplied drive.

NOTES:

1.Maximum continuous bhp for the standard motor is 3.13 (for 208/230 and 460-v units). The maximum continuous watts is 2700 (for 208/230 and 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

2.See page 162 for general fan performance notes.

160

Page 160
Image 160
Bryant 551B, 558F manual FAN PERFORMANCE - 551A155,180 UNITS, PERFORMANCE DATA cont, Glycol Heating Performance