PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

559F240 (20 TONS)

Temp (F)

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

Air Entering

 

6,000/0.075

 

 

7,000/0.085

 

 

 

8,000/0.100

 

 

 

9,000/0.110

 

 

10,000/0.120

 

Condenser

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

62

67

72

57

62

67

72

 

57

62

67

72

 

57

62

67

72

57

62

67

72

 

 

 

 

 

 

 

TC

209

222

246

270

219

228

251

277

 

227

231

256

282

 

234

235

259

286

240

240

262

289

75

 

SHC

209

190

160

130

219

205

171

136

 

227

219

182

143

 

234

231

193

149

240

240

203

156

 

 

kW

15.7

16.0

16.6

17.2

15.9

16.2

16.8

17.4

 

16.2

16.3

16.9

17.6

 

16.4

16.5

17.1

17.7

16.6

16.7

17.2

17.8

 

 

TC

203

214

237

261

212

220

242

267

 

220

224

246

272

 

227

227

250

276

233

233

252

279

85

 

SHC

203

186

157

126

212

201

168

133

 

220

215

179

140

 

227

226

189

147

233

233

200

153

 

 

kW

17.0

17.3

17.9

18.5

17.3

17.5

18.1

18.7

 

17.5

17.6

18.2

18.9

 

17.7

17.8

18.4

19.0

17.9

18.0

18.5

19.2

 

 

TC

197

207

228

252

206

211

233

257

 

213

215

237

261

 

220

220

239

265

225

225

241

267

95

 

SHC

197

182

153

123

206

196

164

130

 

213

210

175

136

 

220

219

185

143

225

225

195

149

 

 

kW

18.5

18.7

19.3

19.8

18.8

18.9

19.4

20.1

 

19.0

19.0

19.6

20.2

 

19.2

19.2

19.8

20.4

19.4

19.4

19.8

20.5

 

 

TC

190

197

218

241

198

202

222

246

 

206

205

226

250

 

212

212

228

254

217

216

230

255

105

 

SHC

190

178

149

119

198

192

160

126

 

206

204

171

133

 

212

211

181

139

217

216

191

145

 

 

kW

20.1

20.1

20.6

21.3

20.3

20.2

20.8

21.5

 

20.5

20.4

21.0

21.7

 

20.7

20.7

21.1

21.8

20.9

20.9

21.3

21.9

 

 

TC

183

188

207

228

191

192

211

233

 

198

197

215

237

 

203

203

217

240

208

207

218

242

115

 

SHC

183

173

145

117

191

187

156

122

 

198

197

166

128

 

203

203

177

135

208

207

186

141

 

 

kW

21.8

21.7

22.1

22.8

22.0

21.9

22.3

22.9

 

22.2

22.0

22.4

23.1

 

22.4

22.2

22.6

23.2

22.5

22.4

22.6

23.3

 

 

TC

175

178

196

217

183

182

200

221

 

189

188

202

224

 

194

194

204

226

199

198

206

227

125

 

SHC

175

168

141

111

183

181

152

117

 

189

188

162

125

 

194

194

172

130

199

198

181

137

 

 

kW

23.6

23.2

23.7

24.3

23.8

23.4

23.8

24.4

 

23.9

23.6

23.9

24.6

 

24.1

23.8

24.1

24.7

24.2

23.9

24.2

24.8

559F180-300

LEGEND

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb

lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb =

tedb

sensible capacity (Btuh)

 

1.10 x cfm

 

 

tlwb =

Wet-bulb temperature corresponding to

 

enthalpy of air leaving evaporator coil (hlwb)

total capacity (Btuh)

hlwb

= hewb

 

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

ENTERING AIR DRY-BULB TEMP (F)

BYPASS FACTOR

79

78

77

76

75

under 75

(BF)

81

82

83

84

85

over 85

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

.10

.98

1.96

2.94

3.92

4.90

Use formula

.20

.87

1.74

2.62

3.49

4.36

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

559F300 (25 TONS)

Temp (F)

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

Air Entering

 

7,000/0.05

 

 

8,000/0.06

 

 

 

9,000/0.07

 

 

 

10,000/0.08

 

 

11,250/0.09

 

Condenser

 

 

 

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

62

67

72

57

62

67

72

 

57

62

67

72

 

57

62

67

72

57

62

67

72

 

 

 

 

 

 

 

TC

256

271

298

328

266

277

304

334

 

275

281

308

339

 

283

286

312

342

292

293

316

346

75

 

SHC

255

232

195

158

266

250

208

167

 

275

265

223

177

 

283

279

235

184

292

291

249

197

 

 

kW

19.1

19.5

20.4

21.2

19.5

19.7

20.6

21.4

 

19.8

19.9

20.7

21.6

 

20.0

20.2

20.9

21.8

20.3

20.4

21.0

21.9

 

 

TC

248

262

287

317

259

267

294

324

 

268

272

298

330

 

275

278

303

334

283

284

306

337

85

 

SHC

248

227

191

155

259

244

203

162

 

268

259

216

170

 

275

271

226

177

283

283

243

189

 

 

kW

21.0

21.4

22.2

23.1

21.4

21.6

22.4

23.3

 

21.7

21.8

22.6

23.5

 

22.0

22.0

22.8

23.7

22.3

22.3

22.9

23.9

 

 

TC

242

252

277

306

251

258

283

312

 

260

261

288

317

 

267

267

291

321

275

274

294

326

95

 

SHC

242

223

187

150

251

240

199

158

 

260

254

210

165

 

267

263

222

172

275

274

236

181

 

 

kW

23.0

23.3

24.1

25.1

23.4

23.6

24.4

25.3

 

23.7

23.8

24.5

25.5

 

24.0

24.0

24.7

25.7

24.3

24.3

24.9

25.8

 

 

TC

234

241

266

293

243

247

272

299

 

251

252

275

302

 

258

257

279

307

265

264

282

311

105

 

SHC

234

218

182

146

243

233

195

153

 

251

246

205

161

 

258

255

217

167

265

264

230

175

 

 

kW

25.1

25.3

26.1

27.0

25.5

25.6

26.4

27.4

 

25.8

25.8

26.5

27.5

 

26.1

26.1

26.7

27.7

26.4

26.3

26.9

27.9

 

 

TC

226

231

254

279

235

236

259

284

 

242

241

261

288

 

248

247

264

291

255

253

267

294

115

 

SHC

226

212

178

141

235

228

189

148

 

242

238

201

156

 

248

247

211

162

255

253

225

170

 

 

kW

27.4

27.4

28.3

29.1

27.7

27.7

28.5

29.3

 

28.0

27.9

28.6

29.5

 

28.2

28.2

28.8

29.7

28.6

28.4

29.0

29.9

 

 

TC

221

224

246

229

229

251

 

236

235

253

 

242

240

256

249

246

258

121

 

SHC

221

209

175

229

223

186

 

236

233

197

 

242

240

208

249

246

221

 

 

kW

28.7

28.7

29.6

29.1

29.0

29.8

 

29.3

29.2

29.9

 

29.6

29.5

30.1

29.9

29.7

30.2

LEGEND

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input ldb — Leaving Dry-Bulb

lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb =

tedb

sensible capacity (Btuh)

 

1.10 x cfm

tlwb =

Wet-bulb temperature corresponding to

 

enthalpy of air leaving evaporator coil (hlwb)

total capacity (Btuh)

hlwb

= hewb

 

4.5 x cfm

 

 

 

3.The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

ENTERING AIR DRY-BULB TEMP (F)

BYPASS FACTOR

79

78

77

76

75

under 75

(BF)

81

82

83

84

85

over 85

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

.10

.98

1.96

2.94

3.92

4.90

Use formula

.20

.87

1.74

2.62

3.49

4.36

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).