Bryant 551B, 551A ACCESSORY/FIOP STATIC PRESSURE in. wg* - 558F180-300, PERFORMANCE DATA cont

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 145
Image 145

PERFORMANCE DATA (cont)

FAN PERFORMANCE — 558F180-300 UNITS (cont)

558F300 (25 TONS)*

Airflow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

0.4

 

 

 

0.6

 

 

 

0.8

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Watts

Rpm

 

Bhp

Watts

Rpm

 

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

 

845

 

3.26

 

2693

 

909

 

3.60

 

2979

969

 

3.96

3272

1028

4.32

3574

1083

4.70

3883

1137

5.08

4,200

7,500

 

896

 

3.82

 

3156

 

956

 

4.17

 

3450

1014

 

4.54

3752

1069

4.91

4060

1123

5.29

4375

1174

5.68

4,698

8,000

 

948

 

4.43

 

3667

 

1005

 

4.80

 

3969

1060

 

5.17

4278

1112

5.56

4593

1163

5.94

4915

1213

6.34

5,243

8,500

 

1001

 

5.11

 

4226

 

1054

 

5.49

 

4537

1106

 

5.87

4853

1156

6.26

5175

1205

6.66

5504

1253

7.06

5,838

9,000

 

1053

 

5.85

 

4836

 

1104

 

6.23

 

5155

1154

 

6.63

5478

1202

7.02

5808

1248

7.43

6142

1294

7.84

6,483

9,500

 

1106

 

6.65

 

5498

 

1155

 

7.04

 

5824

1202

 

7.44

6155

1248

7.85

6492

1293

8.26

6833

1336

8.68

7,179

10,000

 

1159

 

7.52

 

6214

 

1206

 

7.92

 

6547

1251

 

8.33

6886

1295

8.74

7229

1338

9.16

7577

1380

9.59

7,929

10,500

 

1213

 

8.45

 

6984

 

1257

 

8.86

 

7325

1300

 

9.28

7671

1342

9.70

8020

1384

10.13

8375

1424

10.56

8,733

11,000

 

1266

 

9.45

 

7810

 

1309

 

9.87

 

8159

1350

 

10.29

8511

1391

10.73

8868

1431

11.16

9229

1470

11.60

9,594

11,250

 

1293

 

9.97

 

8245

 

1334

 

10.40

 

8597

1375

 

10.83

8953

1415

11.26

9313

1454

11.70

9677

1493

12.15

10,045

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

558F300 (25 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

 

 

1.6

 

 

 

1.8

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

Rpm

 

Bhp

Watts

 

 

 

 

 

 

 

 

 

 

7,000

1189

 

5.47

 

4,524

 

1239

5.87

 

4,854

1288

 

4.91

5191

 

 

 

 

 

 

 

 

 

 

7,500

1224

 

6.08

 

5,026

 

1272

6.48

 

5,362

1320

 

5.56

5703

 

 

 

 

 

 

 

 

 

 

8,000

1261

 

6.75

 

5,577

 

1307

7.16

 

5,917

1353

 

6.26

6263

 

 

 

 

 

 

 

 

 

 

8,500

1299

 

7.47

 

6,177

 

1344

7.89

 

6,523

1388

 

7.02

6873

 

 

 

 

 

 

 

 

 

 

9,000

1338

 

8.26

 

6,828

 

1382

8.68

 

7,179

1424

 

7.85

7534

 

 

 

 

 

 

 

 

 

 

9,500

1379

 

9.11

 

7,530

 

1421

9.54

 

7,887

1462

 

8.74

8247

 

 

 

 

 

 

 

 

 

 

10,000

1421

 

10.02

 

8,286

 

1461

10.46

 

8,648

1501

 

9.70

9014

 

 

 

 

 

 

 

 

 

 

10,500

1464

 

11.00

 

9,096

 

1503

11.45

 

9,464

1541

 

10.73

9835

 

 

 

 

 

 

 

 

 

 

11,000

1508

 

12.05

 

9,963

 

1546

12.50

 

10,336

 

 

 

 

 

 

 

 

 

 

 

11,250

1530

 

12.60

 

10,417

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

NOTES:

1.Maximum continuous bhp is 10.20 (208/230 v) or 11.80 (460 v) and the maximum contin- uous watts are 9510 (208/230 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

2.See below for general fan performance notes.

GENERAL FAN PERFORMANCE NOTES

NOTES:

 

motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor

1.

Values include losses for filters, unit casing, and wet coils. See below for

 

Performance table on page 146 for additional information.

 

accessory/factory-installed option static pressure information.

3.

Use of a field-supplied motor may affect wire sizing. Contact your Bryant

2.

Extensive motor and electrical testing on these units ensures that the full

 

representative for details.

 

range of the motor can be utilized with confidence. Using your fan motors up

4.

Interpolation is permissible. Do not extrapolate.

 

to the wattage ratings shown will not result in nuisance tripping or premature

 

 

OUTDOOR SOUND POWER

UNIT

 

SOUND

A-WEIGHTED

 

 

 

OCTAVE BANDS

 

 

 

558F

 

RATING

(dB)

63

125

250

500

1000

2000

4000

8000

 

(60 Hz) dB

 

 

 

 

 

 

 

 

 

 

 

180

 

88

87.6

90.8

88.7

86.4

84.3

83.5

78.4

75.6

66.8

210

 

88

87.8

90.8

88.7

86.4

84.3

83.5

78.4

75.6

66.8

240

 

95

94.1

90.6

87.2

89.9

86.2

85.8

81.0

75.6

69.6

300

 

95

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

LEGEND

 

 

 

 

 

 

 

 

 

 

dB — Sound Levels (decibels)

ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 558F180-300

COMPONENT

 

 

 

CFM

 

 

5400

6000

7200

9000

10,000

11,250

 

EconoMi$er

0.06

0.07

0.09

0.11

0.12

0.14

Glycol Coil

0.30

0.35

0.44

0.58

0.66

0.77

Electric Heat (kW)

 

 

 

 

 

 

26/32

0.08

0.09

0.11

0.15

0.17

0.20

31

0.08

0.09

0.11

0.15

0.17

0.20

42/56

0.11

0.12

0.15

0.19

0.21

0.24

55

0.11

0.12

0.15

0.19

0.21

0.24

56/75

0.14

0.15

0.20

0.24

0.26

0.29

80

0.14

0.15

0.20

0.24

0.26

0.29

Perfect Humidity™ Dehumidification Package

0.06

0.07

0.10

0.16

0.20

0.25

LEGEND

 

 

 

 

 

 

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

558F180-300

145

Page 145
Image 145
Bryant 551B ACCESSORY/FIOP STATIC PRESSURE in. wg* - 558F180-300, PERFORMANCE DATA cont, General Fan Performance Notes