558F180-210 559F180-216 558F300 558F240 559F240-300
FEATURES/BENEFITS
EASY MAINTENANCE AND INSTALLATION
551B036-072 558F036-073 551B090-150 551A155,180558F090-150
Totally Enclosed Condenser Fan Motors and permanently
Single-Point Electrical Power Connections permit easier
SERVICEABILITY
QUIET, EFFICIENT OPERATION AND DEPENDABLE PERFORMANCE
558F180-300
TABLE OF CONTENTS
Guide Specifications - Sizes
558F036-150
2. Some options may increase product lead times
OPTIONS AND ACCESSORIES
LOW AMBIENT CONTROLS
OPTIONS AND ACCESSORIES cont
BAROMETRIC RELIEF/POWER EXHAUST 155-300 Shown
Dura-Shield Option
DURA-SHIELD CONDENSER COIL OPTIONS
CONDENSER COIL PROTECTION APPLICATIONS
Perfect Humidity DEHUMIDIFICATION PACKAGE
BRYANT COMMERCIAL THERMOSTAT
LIGHT COMMERCIAL THERMIDISTAT
TIME GUARD CONTROL
DURABLADE ECONOMIZER
Factory-installed, internally-mounted, NEC National Electri- cal Code and UL Underwriters’ Laboratories approved non-fused switch provides unit power shutoff with disconnect lockout protection capability. The switch is accessible from outside the unit
UNIT-MOUNTED DISCONNECT Sizes
CONVENIENCE OUTLET
COMPRESSOR HINGED PANEL OPTION 581B090-150 UNITS SHOWN
HAIL GUARD
COIL GUARD GRILLE 036-150 Only
CONTROL BOX HINGED PANEL OPTION 581B036-072 UNITS
581B036-072
EVAPORATOR-FAN HINGED PANEL OPTION
FILTER HINGED PANEL OPTION
LP CONVERSION KIT
OPERATING SEQUENCE - SIZE 090-150 UNITS
CONTROLS
OPERATING SEQUENCE - SIZE 036-073 UNITS
SEQUENCE OF OPERATION SIZES
CONTROLS cont
Perfect Humidity Dehumidification Option
TYPICAL WIRING SCHEMATIC Single Fan Units, Sizes
ACTUATOR
TYPICAL WIRING SCHEMATIC Two-Fan Units, Size
EconoMi$er
TYPICAL WIRING SCHEMATIC Sizes
3. Jumpers are omitted when unit is equipped with EconoMi$er
Non-Fused Disconnect Optional
TYPICAL WIRING SCHEMATIC cont
EconoMi$er Wiring
Horizontal Discharge Ducting
TYPICAL PIPING AND WIRING - SIZES
Vertical Discharge Ducting
2. Installation must comply with all applicable codes
Concentric Duct Distribution Unit Sizes
APPLICATION DATA
10. MAXIMUM OPERATING OUTDOOR-AIR TEMPERATURE
12. PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE
c. MUSEUMS AND LIBRARIES - Humidity can damage books and artwork
APPLICATION DATA cont
Applications
15. PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE FEATURES AND BENEFITS
Pressure Enthalpy Curve
db - Dry Bulb wb - Wet Bulb
Psychrometric Chart 551B072 Shown
Without Subcooler
Point 3 - Leaving Air F 63.0 db/56.8 wb With Subcooler
558F E X 090 000 KB
MODEL NUMBER NOMENCLATURE - 558F
558F036
ARI* CAPACITY RATINGS
558F036
PHYSICAL DATA - 558F036-073
558F036
PHYSICAL DATA - 558F090-150
558F036-150
BASE UNIT DIMENSIONS - 558F036-072
BASE UNIT DIMENSIONS - 558F073
558F036-150
BASE UNIT DIMENSIONS - 558F090,102,120,150
BASE UNIT DIMENSIONS - 558F091,121
ACCESSORY DIMENSIONS
ACCESSORY DIMENSIONS cont
III SELECT ELECTRIC HEAT
SELECTION PROCEDURE with 558F048 example
I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS
II SELECT UNIT BASED ON REQUIRED COOLING CAPACITY
over
PERFORMANCE DATA
COOLING CAPACITIES
COOLING CAPACITIES cont
PERFORMANCE DATA cont
COOLING CAPACITIES cont
558F036-150
PERFORMANCE DATA cont
over
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
4. Interpolation is permissible. Do not extrapolate
GENERAL FAN PERFORMANCE NOTES
FAN RPM AT MOTOR PULLEY SETTINGS
ACCESSORY/FIOP STATIC PRESSURE in. wg - 558F036-073
ACCESSORY/FIOP STATIC PRESSURE* in. wg - 558F090-150
EVAPORATOR-FAN MOTOR EFFICIENCY
EconoMi$er Power Exhaust Performance 558F036-073
EconoMi$er Power Exhaust Performance 558F090-150
OUTDOOR SOUND DATA Total Unit
CONTINUOUS BHP
EVAPORATOR-FAN MOTOR PERFORMANCE
MULTIPLICATION FACTORS
ELECTRIC HEATING CAPACITIES
ELECTRICAL DATA - 558F036-073
ELECTRICAL DATA - 558F036-073 cont
ELECTRICAL DATA - 558F036-073 cont
ELECTRICAL DATA - 558F090-150
ELECTRICAL DATA - 558F090-150 cont
2. Unbalanced 3-Phase Supply Voltage
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES PAGES
551B E X 090 000 DA
MODEL NUMBER NOMENCLATURE - 551B
551B036-150
PHYSICAL DATA - 551B036-072
Acutrol Metering Device
PHYSICAL DATA - 551B090-150
High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins
BASE UNIT DIMENSIONS - 551B036-072
551B036
551B036-150
BASE UNIT DIMENSIONS - 551B090-150
ACCESSORY DIMENSIONS - 551B036-072
ACCESSORY DIMENSIONS - 551B090-150
V DETERMINE NET CAPACITIES
SELECTION PROCEDURE With 551B048 Example
IV DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS
hlwb = hewb
COOLING CAPACITIES, STANDARD UNITS
tldb = tedb
551B036
COOLING CAPACITIES, STANDARD UNITS cont
551B036
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION
551B036
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION cont
PERFORMANCE DATA CONT
551B036
551B036
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
551B036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
551B036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
EVAPORATOR-FAN MOTOR PERFORMANCE - STANDARD MOTOR
FAN RPM AT MOTOR PULLEY SETTING* STANDARD MOTOR/DRIVE
FAN RPM AT MOTOR PULLEY SETTING* HIGH-STATIC MOTOR/DRIVE
ELECTRIC HEATERS STATIC PRESSURE DROP in. wg 551B090-150
ACCESSORY/FIOP ECONOMIZERS AND
EVAPORATOR-FAN MOTOR PERFORMANCE - HIGH-STATIC MOTORS
ELECTRIC HEATERS STATIC PRESSURE DROP in. wg 551B036-072
EconoMi$er Power Exhaust Performance 551B036-072
Vertical EconoMi$er Barometric Relief Damper Characteristics
Horizontal EconoMi$er Barometric Relief Damper Characteristics
EconoMi$er Power Exhaust Performance
Horizontal EconoMi$er Return-Air Pressure Drop
OUTDOOR SOUND POWER TOTAL UNIT
Vertical EconoMi$er Outdoor-Air Leakage
Vertical EconoMi$er Return-Air Pressure Drop
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES
STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
ELECTRICAL DATA
STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET cont
ELECTRICAL DATA cont
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET cont
HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
551B120††
HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET cont
551B090††
551B102††
HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET cont
PART 2 - PRODUCTS
GUIDE SPECIFICATIONS - SIZES
558F/551B036-150
PART 1 - GENERAL
GUIDE SPECIFICATIONS - SIZES 036-150 cont
13. High-Static Motor and Drive 036-120 3-phase units only
LOW OUTDOOR TEMPERATURE OPERATING LIMITS F
MODEL NUMBER NOMENCLATURE - 559F
5 5 9 F E X 1 8 0 0 0 0 A H C B
AIR QUANTITY LIMITS
ELECTRIC RESISTANCE HEATER DATA - 559F180-300
559F180-300
ARI* CAPACITY RATINGS cont
Copper Plate Fins, Face Split
PHYSICAL DATA - 559F180-300
Aluminum Pre-Coated, or Copper Plate Fins
PHYSICAL DATA - 559F180-300 cont
OPERATING AND RIGGING WEIGHTS
OPTIONS AND ACCESSORIES Weight Adders
300-559F180
BASE UNIT DIMENSIONS - 559F180-216
BASE UNIT DIMENSIONS - 559F240-300
DIMENSIONS degrees and inches
Horizontal and Vertical Roof Curbs and Horizontal Adapter Curb
Barometric Relief/Power Exhaust
Horizontal Supply/Return Adapter Installation
K.O. - Knockout
Factory-Installed Convenience Outlet
Factory-Installed Non-Fused Disconnect
IV DETERMINE NET COOLING CAPACITY
SELECTION PROCEDURE with 559F180 example
III DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS
I DETERMINE COOLING REQUIREMENTS AT DESIGN CONDITIONS
over
over
Above 80 F edb, add corr factor x cfm to SHC
hlwb =
559F180
tldb
tlwb =
FAN PERFORMANCE - 559F180-300 UNITS
GLYCOL HEATING PERFORMANCE
FAN PERFORMANCE - 559F180-300 UNITS cont
559F180
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F216-300
OUTDOOR SOUND POWER
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F180
High Static Regain Adapter
Fan Performance Using Accessory Power Exhaust 559F180-300
Horizontal Supply/Return Fan Performance with CRRFCURB013A00
20 Tons
3 Ph, 60 Hz
559F180-300
5 5 8 F E X 2 1 0 0 0 0 A A A A
MODEL NUMBER NOMENCLATURE - 558F180-300
558F180-300
3750
ELECTRIC RESISTANCE HEATER DATA - 558F180-300
558F180
PHYSICAL DATA - 558F180-300
PHYSICAL DATA - 558F180-300 cont
BASE UNIT DIMENSIONS - 558F180
558F180
BASE UNIT DIMENSIONS - 558F240
BASE UNIT DIMENSIONS - 558F300
Side supply and
Standard curb
Standard curb for
units requiring
Horizontal Adapter
PACKAGE NO
2 ′-0 ″
Pre-Assembled, High Static
558F180-300
SELECTION PROCEDURE with 558F240 Example
COOLING CAPACITIES
COOLING CAPACITIES LEGEND AND NOTES
This accessory glycol coil is intended for use with a MINIMUM of 25% glycol
558F180
FAN PERFORMANCE - 558F180-300 UNITS
FAN PERFORMANCE - 558F180-300 UNITS cont
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 558F180-300
Fan Performance Using Accessory Power Exhaust 558F180-300
ELECTRICAL DATA - 558F180-300
ELECTRICAL DATA - 558F180-300 cont
COOLING OPERATION AIR QUANTITY LIMITS
MODEL NUMBER NOMENCLATURE - 551A
551A155-180
551A E X 155 000 AJ C B
INDOOR SOUND DATA TOTAL UNIT
ELECTRIC RESISTANCE HEATER DATA
Face Split
PHYSICAL DATA - 551A155,180
Weight Adders
OPTIONS AND ACCESSORIES
PHYSICAL DATA cont
BASE UNIT DIMENSIONS - 551A155,180
551A155-180
ACCESSORY DIMENSIONS
551A155-180
ACCESSORY DIMENSIONS cont
Horizontal Supply/Return Adapter Installation
Barometric Relief/Power Exhaust
551A155-180
V DETERMINE NET COOLING CAPACITIES
SELECTION PROCEDURE
VI SELECT THE UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE
FACTOR
BYPASS
ENTERING AIR DRY-BULB TEMP F
FACTOR
ENTERING AIR DRY-BULB TEMP F
551A155
under
551A155
FAN PERFORMANCE - 551A155,180 UNITS
FAN PERFORMANCE - 551A155,180 UNITS cont
ACCESSORY/FIOP STATIC PRESSURE in. wg - 551A155,180 UNITS
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 551A155,180
EVAPORATOR FAN MOTOR PERFORMANCE
Fan Performance Using Accessory Power Exhaust 551A155,180
551A155
ELECTRICAL DATA - 551A155,180
551A/558F/559F155-300
gas passing through motor windings and shall have
GUIDE SPECIFICTIONS - SIZES 155-300 cont
1. Unit shall be capable of starting and running at 125 F
ambient outdoor temperature per maximum load cri
GUIDE SPECIFICATIONS - SIZES 155-300 cont
551A/558F/559F155-300
50-60
INDEX
21-25
89-92
Printed in U.S.A
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS