Bryant 551B, 551A ELECTRIC RESISTANCE HEATER DATA - 558F180-300, ARI* CAPACITY RATINGS cont, 3750

Models: 551A 551B 558F

1 170
Download 170 pages 34.1 Kb
Page 130
Image 130

ARI* CAPACITY RATINGS (cont)

ELECTRIC RESISTANCE HEATER DATA — 558F180-300

UNIT

 

HEATER kW

 

HEATER

HEAT

MAXIMUM

 

MINIMUM

 

Unit Voltages

 

HEATING CFM

558F

 

 

STAGES

PER STAGE

STAGES*

 

208

230

460

575

 

 

 

Cfm

 

L/s

 

26

31

30

2

50/50

2

 

 

 

180

42

52

50

2

33/67

3

3750

 

1770

 

56

69

73

2

50/50

4

 

 

 

 

26

34

32

2

50/50

2

 

 

 

210

42

56

55

2

33/67

3

5400

 

2549

 

56

75

80

2

50/50

4

 

 

 

 

26

31

30

2

50/50

2

 

 

 

240

42

52

50

2

33/67

3

5000

 

2360

 

56

69

73

2

50/50

4

 

 

 

 

26

34

32

2

50/50

2

 

 

 

300

42

56

55

2

33/67

3

7000

 

3304

 

56

75

80

2

50/50

4

 

 

 

*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-ambient kit.

NOTE: Heaters are rated at 240, 480, and 600 v. Use the Multiplication Factors table below to determine heater capacity for your particular voltage.

MULTIPLICATION FACTORS

HEATER RATING

 

 

 

 

ACTUAL HEATER VOLTAGE

 

 

 

 

VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

600

0.840

0.918

1.000

NOTE: The following equation converts kW of heat energy to Btuh:

EXAMPLE: 34 kW (at 230 v) heater on 208 v

kW x 3.413 = Btuh.

= 34.0 (.751 mult factor)

 

= 25.5 kW capacity at 208 v.

558F180-300

130

Page 130
Image 130