EASY MAINTENANCE AND INSTALLATION
FEATURES/BENEFITS
551B036-072 558F036-073 551B090-150 551A155,180558F090-150
558F180-210 559F180-216 558F300 558F240 559F240-300
SERVICEABILITY
Single-Point Electrical Power Connections permit easier
QUIET, EFFICIENT OPERATION AND DEPENDABLE PERFORMANCE
Totally Enclosed Condenser Fan Motors and permanently
Guide Specifications - Sizes
TABLE OF CONTENTS
558F036-150
558F180-300
2. Some options may increase product lead times
OPTIONS AND ACCESSORIES
OPTIONS AND ACCESSORIES cont
BAROMETRIC RELIEF/POWER EXHAUST 155-300 Shown
LOW AMBIENT CONTROLS
CONDENSER COIL PROTECTION APPLICATIONS
DURA-SHIELD CONDENSER COIL OPTIONS
Perfect Humidity DEHUMIDIFICATION PACKAGE
Dura-Shield Option
TIME GUARD CONTROL
LIGHT COMMERCIAL THERMIDISTAT
DURABLADE ECONOMIZER
BRYANT COMMERCIAL THERMOSTAT
UNIT-MOUNTED DISCONNECT Sizes
CONVENIENCE OUTLET
Factory-installed, internally-mounted, NEC National Electri- cal Code and UL Underwriters’ Laboratories approved non-fused switch provides unit power shutoff with disconnect lockout protection capability. The switch is accessible from outside the unit
COIL GUARD GRILLE 036-150 Only
HAIL GUARD
CONTROL BOX HINGED PANEL OPTION 581B036-072 UNITS
COMPRESSOR HINGED PANEL OPTION 581B090-150 UNITS SHOWN
FILTER HINGED PANEL OPTION
EVAPORATOR-FAN HINGED PANEL OPTION
LP CONVERSION KIT
581B036-072
CONTROLS
OPERATING SEQUENCE - SIZE 036-073 UNITS
OPERATING SEQUENCE - SIZE 090-150 UNITS
SEQUENCE OF OPERATION SIZES
CONTROLS cont
Perfect Humidity Dehumidification Option
TYPICAL WIRING SCHEMATIC Single Fan Units, Sizes
TYPICAL WIRING SCHEMATIC Two-Fan Units, Size
EconoMi$er
ACTUATOR
TYPICAL WIRING SCHEMATIC Sizes
3. Jumpers are omitted when unit is equipped with EconoMi$er
TYPICAL WIRING SCHEMATIC cont
EconoMi$er Wiring
Non-Fused Disconnect Optional
TYPICAL PIPING AND WIRING - SIZES
Vertical Discharge Ducting
Horizontal Discharge Ducting
2. Installation must comply with all applicable codes
10. MAXIMUM OPERATING OUTDOOR-AIR TEMPERATURE
APPLICATION DATA
12. PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE
Concentric Duct Distribution Unit Sizes
APPLICATION DATA cont
Applications
c. MUSEUMS AND LIBRARIES - Humidity can damage books and artwork
15. PERFECT HUMIDITY DEHUMIDIFICATION PACKAGE FEATURES AND BENEFITS
Pressure Enthalpy Curve
Without Subcooler
Psychrometric Chart 551B072 Shown
Point 3 - Leaving Air F 63.0 db/56.8 wb With Subcooler
db - Dry Bulb wb - Wet Bulb
558F036
MODEL NUMBER NOMENCLATURE - 558F
ARI* CAPACITY RATINGS
558F E X 090 000 KB
558F036
PHYSICAL DATA - 558F036-073
558F036
PHYSICAL DATA - 558F090-150
558F036-150
BASE UNIT DIMENSIONS - 558F036-072
BASE UNIT DIMENSIONS - 558F073
558F036-150
BASE UNIT DIMENSIONS - 558F090,102,120,150
BASE UNIT DIMENSIONS - 558F091,121
ACCESSORY DIMENSIONS
ACCESSORY DIMENSIONS cont
I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS
SELECTION PROCEDURE with 558F048 example
II SELECT UNIT BASED ON REQUIRED COOLING CAPACITY
III SELECT ELECTRIC HEAT
PERFORMANCE DATA
COOLING CAPACITIES
over
COOLING CAPACITIES cont
PERFORMANCE DATA cont
558F036-150
PERFORMANCE DATA cont
COOLING CAPACITIES cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
558F036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
558F036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
4. Interpolation is permissible. Do not extrapolate
GENERAL FAN PERFORMANCE NOTES
ACCESSORY/FIOP STATIC PRESSURE in. wg - 558F036-073
ACCESSORY/FIOP STATIC PRESSURE* in. wg - 558F090-150
FAN RPM AT MOTOR PULLEY SETTINGS
EconoMi$er Power Exhaust Performance 558F090-150
EconoMi$er Power Exhaust Performance 558F036-073
OUTDOOR SOUND DATA Total Unit
EVAPORATOR-FAN MOTOR EFFICIENCY
CONTINUOUS BHP
EVAPORATOR-FAN MOTOR PERFORMANCE
MULTIPLICATION FACTORS
ELECTRIC HEATING CAPACITIES
ELECTRICAL DATA - 558F036-073
ELECTRICAL DATA - 558F036-073 cont
ELECTRICAL DATA - 558F036-073 cont
ELECTRICAL DATA - 558F090-150
ELECTRICAL DATA - 558F090-150 cont
2. Unbalanced 3-Phase Supply Voltage
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES PAGES
MODEL NUMBER NOMENCLATURE - 551B
551B036-150
551B E X 090 000 DA
PHYSICAL DATA - 551B036-072
PHYSICAL DATA - 551B090-150
High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Acutrol Metering Device
BASE UNIT DIMENSIONS - 551B036-072
551B036
551B036-150
BASE UNIT DIMENSIONS - 551B090-150
ACCESSORY DIMENSIONS - 551B036-072
ACCESSORY DIMENSIONS - 551B090-150
SELECTION PROCEDURE With 551B048 Example
IV DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS
V DETERMINE NET CAPACITIES
COOLING CAPACITIES, STANDARD UNITS
tldb = tedb
hlwb = hewb
551B036
COOLING CAPACITIES, STANDARD UNITS cont
551B036
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION
551B036
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION cont
PERFORMANCE DATA CONT
551B036
551B036
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
FAN PERFORMANCE - VERTICAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS
PERFORMANCE DATA cont
551B036-150
PERFORMANCE DATA cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
PERFORMANCE DATA cont
551B036-150
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
FAN PERFORMANCE - HORIZONTAL DISCHARGE UNITS cont
FAN RPM AT MOTOR PULLEY SETTING* STANDARD MOTOR/DRIVE
FAN RPM AT MOTOR PULLEY SETTING* HIGH-STATIC MOTOR/DRIVE
EVAPORATOR-FAN MOTOR PERFORMANCE - STANDARD MOTOR
EVAPORATOR-FAN MOTOR PERFORMANCE - HIGH-STATIC MOTORS
ACCESSORY/FIOP ECONOMIZERS AND
ELECTRIC HEATERS STATIC PRESSURE DROP in. wg 551B036-072
ELECTRIC HEATERS STATIC PRESSURE DROP in. wg 551B090-150
Horizontal EconoMi$er Barometric Relief Damper Characteristics
Vertical EconoMi$er Barometric Relief Damper Characteristics
EconoMi$er Power Exhaust Performance
EconoMi$er Power Exhaust Performance 551B036-072
Vertical EconoMi$er Outdoor-Air Leakage
OUTDOOR SOUND POWER TOTAL UNIT
Vertical EconoMi$er Return-Air Pressure Drop
Horizontal EconoMi$er Return-Air Pressure Drop
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES
STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
ELECTRICAL DATA
STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET cont
ELECTRICAL DATA cont
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET cont
HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
551B090††
HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET cont
551B102††
551B120††
HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET cont
558F/551B036-150
GUIDE SPECIFICATIONS - SIZES
PART 1 - GENERAL
PART 2 - PRODUCTS
GUIDE SPECIFICATIONS - SIZES 036-150 cont
13. High-Static Motor and Drive 036-120 3-phase units only
5 5 9 F E X 1 8 0 0 0 0 A H C B
MODEL NUMBER NOMENCLATURE - 559F
AIR QUANTITY LIMITS
LOW OUTDOOR TEMPERATURE OPERATING LIMITS F
559F180-300
ARI* CAPACITY RATINGS cont
ELECTRIC RESISTANCE HEATER DATA - 559F180-300
PHYSICAL DATA - 559F180-300
Aluminum Pre-Coated, or Copper Plate Fins
Copper Plate Fins, Face Split
OPERATING AND RIGGING WEIGHTS
OPTIONS AND ACCESSORIES Weight Adders
PHYSICAL DATA - 559F180-300 cont
300-559F180
BASE UNIT DIMENSIONS - 559F180-216
BASE UNIT DIMENSIONS - 559F240-300
DIMENSIONS degrees and inches
Horizontal and Vertical Roof Curbs and Horizontal Adapter Curb
Barometric Relief/Power Exhaust
Horizontal Supply/Return Adapter Installation
Factory-Installed Convenience Outlet
Factory-Installed Non-Fused Disconnect
K.O. - Knockout
III DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS
SELECTION PROCEDURE with 559F180 example
I DETERMINE COOLING REQUIREMENTS AT DESIGN CONDITIONS
IV DETERMINE NET COOLING CAPACITY
over
559F180-300
Above 80 F edb, add corr factor x cfm to SHC
tldb
559F180
tlwb =
hlwb =
FAN PERFORMANCE - 559F180-300 UNITS
GLYCOL HEATING PERFORMANCE
FAN PERFORMANCE - 559F180-300 UNITS cont
559F180
OUTDOOR SOUND POWER
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F180
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 559F216-300
Fan Performance Using Accessory Power Exhaust 559F180-300
Horizontal Supply/Return Fan Performance with CRRFCURB013A00
High Static Regain Adapter
20 Tons
3 Ph, 60 Hz
559F180-300
MODEL NUMBER NOMENCLATURE - 558F180-300
558F180-300
5 5 8 F E X 2 1 0 0 0 0 A A A A
3750
ELECTRIC RESISTANCE HEATER DATA - 558F180-300
558F180
PHYSICAL DATA - 558F180-300
PHYSICAL DATA - 558F180-300 cont
BASE UNIT DIMENSIONS - 558F180
558F180
BASE UNIT DIMENSIONS - 558F240
BASE UNIT DIMENSIONS - 558F300
Standard curb for
Standard curb
units requiring
Side supply and
2 ′-0 ″
PACKAGE NO
Pre-Assembled, High Static
Horizontal Adapter
Factory-Installed Convenience Outlet
SELECTION PROCEDURE with 558F240 Example
PERFORMANCE DATA cont
COOLING CAPACITIES LEGEND AND NOTES
This accessory glycol coil is intended for use with a MINIMUM of 25% glycol
558F180
FAN PERFORMANCE - 558F180-300 UNITS
FAN PERFORMANCE - 558F180-300 UNITS cont
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 558F180-300
Fan Performance Using Accessory Power Exhaust 558F180-300
ELECTRICAL DATA - 558F180-300
ELECTRICAL DATA - 558F180-300 cont
551A155-180
MODEL NUMBER NOMENCLATURE - 551A
551A E X 155 000 AJ C B
COOLING OPERATION AIR QUANTITY LIMITS
INDOOR SOUND DATA TOTAL UNIT
ELECTRIC RESISTANCE HEATER DATA
Face Split
PHYSICAL DATA - 551A155,180
OPTIONS AND ACCESSORIES
PHYSICAL DATA cont
Weight Adders
BASE UNIT DIMENSIONS - 551A155,180
551A155-180
ACCESSORY DIMENSIONS
Horizontal Supply/Return Adapter Installation
ACCESSORY DIMENSIONS cont
Barometric Relief/Power Exhaust
551A155-180
Factory-Installed Convenience Outlet
SELECTION PROCEDURE
VI SELECT THE UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE
V DETERMINE NET COOLING CAPACITIES
BYPASS
ENTERING AIR DRY-BULB TEMP F
FACTOR
551A155
ENTERING AIR DRY-BULB TEMP F
under
FACTOR
551A155
FAN PERFORMANCE - 551A155,180 UNITS
FAN PERFORMANCE - 551A155,180 UNITS cont
ACCESSORY/FIOP STATIC PRESSURE in. wg - 551A155,180 UNITS
ACCESSORY/FIOP STATIC PRESSURE in. wg* - 551A155,180
EVAPORATOR FAN MOTOR PERFORMANCE
Fan Performance Using Accessory Power Exhaust 551A155,180
551A155
ELECTRICAL DATA - 551A155,180
551A/558F/559F155-300
1. Unit shall be capable of starting and running at 125 F
GUIDE SPECIFICTIONS - SIZES 155-300 cont
ambient outdoor temperature per maximum load cri
gas passing through motor windings and shall have
GUIDE SPECIFICATIONS - SIZES 155-300 cont
551A/558F/559F155-300
21-25
INDEX
89-92
50-60