Figure 53: Pilot Burner Flame, Honeywell Q350
Figure 54: Pilot Burner Flame, Honeywell Q327
Figure 55: Pilot Burner Flame, Honeywell Q348
Figure 56: 40mm Main Burner Flame
Figure 57: 1" Main Burner Flame
F.Check pilot burner flame and main burner flames through observation port.
1.Check pilot flame.
a.Continuous Ignition (Standing Pilot), Models IN3 through IN7. See Figure 53. Pilot burner produces a single flame. Flame should be steady, medium hard blue enveloping 3/8 to ½ inch of thermocouple.
b.Continuous Ignition (Standing Pilot), Models IN8 through IN12. See Figure 54. Pilot burner produces three (3) flames. Center flame should be steady, medium hard blue enveloping 3/8 to ½ inch of thermocouple.
c.Electronic Ignition (EI), Models IN3 through IN12. See Figure 55. Pilot should be lit only after completing Step 3. Pilot burner produces three (3) flames. Center flame should be steady, medium hard blue enveloping 3/8 to ½ inch of sensing probe.
CAUTION
Avoid operating this boiler in an environment where saw dust, loose insulation fibers, dry wall dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.