Example 6 - Changing Reset Type

Temperature Reset Based on External Temperature - If de- sired, temperature reset can be based on an external tem- perature, such as space or outdoor-air temperature. This re- quires a thermistor (TlO, Part No. 30GB660002) located in the space or outdoor air and wired to terminals as follows (also see Field Wiring section on page 71):

4 in/4 out Module - 57-15 and J7-16.

At the field configuration step, select external tempera-

ture reset by entering q when CRTYP 0 appears. Then enter set points as described previously in Example 5. See Fig. 5.

Temperature Reset Based on 4-20 mA Signal- If desired,

temperature reset can be based on a 4-20 mA signal. For proper connections, refer to Field Wiring section on page 71 and Fig. 6.

At the field configuration step, select 4-20 mA reset by entering q when CRTYP 0 appears. Then enter set points as described previously in Example 5. See Fig. 7,

Demand Limit, 2-Stage Switch Control - This control has been designed to accept demand limit signals from a build- ing load shedding control. The demand limit function pro- vides for 2 capacity steps. The keypad is used to set the 2 demand limit set points, which range from 100 to 0% of capacity. Capacity steps are controlled by 2 field-supplied relay contacts connected to the designated chiller terminals. (See Field Wiring section on page 7 1 and Fig. 6.)

Example 6 - Changing Reset Type

To change type of reset, first log on as shown in Table 11. Also refer to Set Point Function section, page 39, for information on entering reset set points using reset feature.

KEYPAD

DISPLAY

 

COMMENTS

ENTRY

RESPONSE

 

 

 

 

 

 

Field

configuration

 

FLD CFG

subfunction of

 

 

 

service function

 

CSPTYP 0

Scroll

past single cooling

 

set point

 

 

 

 

CRTYP 0

No reset has been

 

selected

 

 

 

 

 

 

Return water temperature

 

CRTYP 1

reset is selected and

 

 

 

activated

 

 

 

Reset type is changed to

 

CRTYP 2

space or outdoor-air

 

temperature reset and

 

 

 

 

 

 

activated

 

 

 

Reset type is changed to

 

CRTYP 3

4-20 mA signal reset

 

 

 

and

activated

 

CRTYP 0

Reset is deactivated

 

 

 

 

 

10 -

Y- 18

8- 16 ?-

8

6

2-

8- 16 ?-I -

O-

RESET REFERENCE TEMPERATURE (OUTDOOR AIR Fig. 5 - Cooling External Temperature Reset1OR SPACE TEMP