130 (50 Hz),
1.Install control wiring. The minimum wire size for in- stallation is 16 AWC (American Wire Gage). Refer to Fig. 24 and 25 for proper wiring. Open the control box door. Locate unloader relays A and B (URA, URB) in place of the hot gas bypass relays as shown on the com- ponent arrangement diagram on the unit. Mount the re- lays with the
2Wire the control side. Wire the URA coil in series be- tween
Locate the black wire in the control harness originating from TRANS labeled
3.Wire in the solenoid valves.
NOTE: Wires external to the control box must be run in conduit +
Terminal blocks are provided for easy field wiring. Use one of the isolated
4.Configure the microprocessor, Once the relays are mounted in the control box, the microprocessor must be config- ured for the unloader option. ‘To do so:
a.Be sure the
b.Log into the processor and enter the service func- t i o n u s i n g t h e k e y p a d a n d d i s p l a y m o d u l e .
Type r\ I;;;;E] . The keypad LCD will display
“PASSWORD.” Enter ~~1~~~~, and the keypad LCD will display “LOGGEDON. ”
C, To change the configuration, type 14 H, and the keypad LCD will display “FLD CFG.” Press m
until either “NULA 0” or “NULA I” is displayed (depending on the number of unloaders provided as
standard), Then press m H (for 1 unloader on Al)
or FiFi (for 2 unloaders on compressor Al). The d i s p l a y w i l l n o w r e a d e i t h e r “ N U L A 1 ” o r
‘ ‘NULA 2, ” as appropriate, Press I)I to get to the NULB display, and change this setting in the same manner as with circuit A.
d.Once the configuration is complete, press m Fi, and the keypad LCD will display “LOGGEDON,”
Press @ until the keypad LCD display reads “LOG
OFF.” Press H and the keypad LCD will display “EXIT LOG.”
5 Once the unloader heads are installed, the unit is checked.
a. Press T;1H, and the display will read “COMP.”
b. Press the q to scroll down until the display reads “CPA1 OFF.”
c. Press ENTR , and the compressor should start. 0
d.Press a + , and the compressor should stop.
e.Press c + l until the display reads “ULAl OFF.”
f.Press H , and the solenoid should energize.
g.Press q and the solenoid should deenergize.
h.Use the a and H keys to check the remainder of the unloader coils.
6.Once the check has been performed, return the LOCAL/
7.Close and secure the control box door.
8.Start the unit and confirm that the chiller operates properly.
|
| LEGEND |
|
|
|
|
COM | - | Communications Bus |
| - Terminal | Block | |
HGBPR | - | Hot Gas Bypass Relay | TLN | - | Transformer | |
KB | 1 | Normally Open |
| - | Unloader |
|
Snubber | kl | - Unloader | Relay |
Fig. 24 - Flotronic’” II
70