Possible causes of fault are low refrigerant charge, plugged filter drier, or a faulty EXV or thermistor.
Code 48 Low suction superheat, Circuit A Code 49 Low suction superheat, Circuit B
If EXV is at minimum position, suction superheat is less than 10” F (5.5” C) or saturated evaporator temperature is greater than MOP (maximum operating pressure) for more than 5 minutes, affected circuit shuts down after going through pumpout process, Reset is manual with LOCAL/ENABLE-
Possible causes of fault are faulty EXV or thermistor. Code 50 Illegal configuration
This fault indicates a configuration error. Unit is not al- lowed to start. Check all configuration data and set points and correct any errors.
Code 51 Initial configuration required
i2G7
This fault indicates factory configuration has not been done, and unit is not allowed to start. Refer to unit wiring label diagrams for factory configuration codes, There are 8 groups of
4groups must be entered under s17ubafu n c t i o n . G r o u p s
7and 8 must be entered under MHs u b f u n c t i o n .
Enter each group, then press the H key. Use the
down arrow 0+ after each group to bring up the next
empty screen. Unit should start after factory and field con- figurations are correctly entered.
The usual cause of this fault is replacement of the pro- cessor module. Refer to instructions accompanying the re- placement module.
Code 52 Emergency stop by CCN command.
Unit goes through normal shutdown when this command is received, and goes through normal
S T A N D A R D : | 50 | H z | r - - - - | I - - - - | - - |
60 | H z | , | [CPCS | ’ Sl | |
|
|
| 1 C R ’ S |
|
|
|
|
|
|
| LEGEND |
S T A N D A R D : | 070 50 | Hz |
|
|
| Contactor | |
|
|
|
|
|
| ||
A C C E S S O R Y : | 60 | 50 | H z | &I |
| Circuit | Breaker |
| 60 | C O M M |
| Communications Bus | |||
|
|
|
|
| |||
|
|
|
| CPCS |
| Compressor Protection | |
|
|
|
|
|
| Control | Module |
|
|
|
| CR |
| Compressor Contactor Relay | |
|
|
|
| D G T |
| Discharge Gas Thermostat (Optional) | |
|
|
|
| DSIO |
| Relay | Module (Low Voltage) |
|
|
|
| HPS | - | ||
|
|
|
|
| Low Vottage | ||
|
|
|
| K |
| Plug |
|
|
|
|
| PWR |
| Power |
|
|
|
|
| SNB | - | Snubber | |
|
|
|
| TB | Terminal Block | ||
|
|
|
| TRAN | - | Transformer | |
|
|
|
| U | - | Unloader |
Fig. IOA - 24-V Safety Circuit Wiring (040-070)
52