Table 9 - Keypad Directory (cant)

Table 9 - Keypad Directory (cant)

TEST (cant)

During compressor test, compressors start and run for 10 seconds. Compressor service valves and liquid line valves must be open. Energize crankcase heaters 24 hours prior to performing compressor tests.

SUBFUNCTION

KEYPAD ENTRY

2 COMPRESSORS AND UNLOADERS

DISPLAY

COMMENT

 

 

 

 

 

C O M P

 

Compressor and Unloader Test

 

CPA1 X

Test Compressor Al

 

CPA2 X*

Test Compressor

A2T

 

CPA3 X*

Test Compressor

A3t

 

CPA4 X*

Test Compressor

A4t

 

CPBl

X

Test Compressor

Bl

 

CPB2

x*

Test Compressor

B2t

 

CPB3 X*

Test Compressor

B3T

 

CPB4 X*

Test Compressor

B4T

 

ULAl

X

Energize Unloader Al T

 

ULA2

X*

Energize Unloader A2T

 

ULBl X

Energize Unloader Bl t

 

ULB2

X*

Energize Unloader B2t

 

 

 

 

 

 

 

 

 

 

 

SCHEDULE

The Schedule function key CHD is used to configure the occupancy schedule The clock select subfunction can be used for El

unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function described is for clock 1, which is the internal clock. Password required for all subfunctions except override.

 

SUBFUNCTION

1

 

KEYPAD ENTRY

I

DISPLAY

I

COMMENT

 

 

 

 

 

 

 

 

 

 

 

 

 

1 OVERRIDE

 

 

 

 

 

I

OVRD X

 

 

Number of Override Hrs (0 - 4 Hrs)

 

 

 

 

 

 

 

 

 

 

 

 

For example, to extend current occupied mode for 3 hrs, press:

 

 

 

 

 

 

 

 

 

 

ppii-j

 

OVRD 3

 

 

Extended Occupied Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 CLOCK SELECT

 

 

 

/qzq

 

CLOCK XX

 

 

Type of Clock Control

 

 

 

 

 

 

 

 

 

 

 

0 = No Clock, 1 = Clock 1 (Internal)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

*Must be configured

 

 

- Carrier Comfort

Network

 

 

 

 

tlf applicable.

 

 

 

~~”

- Electronic Expansion Valve

 

 

 

 

 

 

 

 

M O P

- Maximum Operating Pressure

 

 

 

 

 

 

 

 

33