Carrier 040-420 specifications 4-20mA Cooling Temperature Reset

Models: 040-420

1 76
Download 76 pages 29.3 Kb
Page 43
Image 43
Fig. 7 - 4-20 mA Cooling Temperature Reset

16

8

6

0

0

2

4

6

8

IO

12

14

16

1 8

2 0

RESET REFERENCE SIGNAL (4 - 20 MA INPUT)

Fig. 7 - 4-20 mA Cooling Temperature Reset

Example 7A - Using Demand Limit (First Log On as Shown in Table 11)

Example 7B - Using Demand Limit (4-20 mA) (First Log On As Shown in Table 11)

KEYPAD DISPLAY

ENTRY RESPONSE

FLD CFG

ERTYP 0

LSTYP 0

LSTYP 1

DEMAND

DLSl 100

DLSl 60

DLS2 100

DLS2 40

To Disable Demand Limit:

COMMENTS

Field configuration sub- function of service function

Scroll past other elements in the subfunction

Loadshed is not enabled

Loadshed is now enabled for 2-stage switch control

Demand Limit set points subfunction of set point function

Loadshed 1 currently set at 100%

Loadshed reset to 60%

Loadshed 2 currently set at 100%

Loadshed 2 reset to 40%

KEYPAD

 

DISPLAY

 

 

COMMENTS

 

ENTRY

 

RESPONSE

 

 

 

 

 

 

 

 

ppiq

 

FLD CFG

Field

configuration

subfunction

 

of service function

 

 

 

 

 

 

 

 

 

t

 

ERTYP 0

Scroll past other elements in

 

 

the

subfunction

 

0

 

 

 

 

 

 

Cl

 

LSTYP 0

Loadshed

is not enabled

 

 

 

 

 

 

 

 

 

q ‘nENTR

 

LSTYP

2

Loadshed

is now enabled

 

 

for 4-20 mA signal control

 

MH

 

DEMAND

Demand

Limit set

points

 

 

 

 

DMAX

100

Maximum demand limit is 100%

 

 

 

 

DMAX

90

Maximum demand limit is 90%

 

 

 

 

RMAX 20

Maximum

demand

limit

 

 

 

 

reference is 20 mA

 

 

 

 

 

 

 

 

 

 

 

 

RMAX

15

Maximum

demand

limit

 

 

 

 

reference is 15 mA

 

 

 

 

 

 

 

 

 

 

 

 

DMIN

0

Minimum demand limit is 0%

 

 

 

 

DMIN

20

Minimum demand limit is 20%

 

 

 

 

RMIN

4

Minimum

demand

limit

 

 

 

 

 

 

 

 

KEYPAD

DISPLAY

 

COMMENTS

ENTRY

RESPONSE

 

 

 

 

 

 

FLD CFG

 

Field configuration sub-

 

 

 

 

 

 

function

of servicefunction

 

 

 

 

 

 

 

ERTYP 0

 

Scroll past other elements

 

 

I

in the

subfunction

 

 

 

 

 

 

 

 

 

 

 

 

LSTYP

1

 

Loadshed

is enabled for

 

 

 

2-stage switch control

 

 

 

 

 

 

 

LSTYP

0

 

Loadshed

is now disabled

 

 

 

 

 

 

 

 

reference is 4

mA

RMlN 6

Minimum demand limit

reference is 6

mA

 

NOTE: Select 3 for Carrier comfort Network (CCN) load limiting Select 4 for CCN demand limiting.