ACCESSORY UNLOADER INSTALLATION
Some of the 30G FlotronicT” II units come standard with unloader(s), and many permit additional unloader(s) to be added if desired. See Table 18.
IMPORTANT: Accessory hot gas bypass cannot be installed with accessory unloaders on units with more than 4 compressors.
If accessory unloaders are desired, an accessory unloader package is used. Package includes a suction cutoff unloader head package. The
NOTE: The accessory package will include all necessary
components and wiring with the following exceptions: The field must provide screws, and on the
Table 18 - Standard and Accessory Unloaders
I |
| 1NO. OF ACCESSORY | ||||
|
|
| Circuit | A |
| Circuit B |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| 1 |
|
| 1 or2 |
|
|
|
|
|
|
|
|
|
| 1 |
|
| 1 |
0 |
| 1 |
|
| 1 | |
|
|
|
|
|
|
|
3OGT225,250,280 | 0 |
| 1 |
|
| 1 |
|
|
|
|
|
|
|
*And associated modular units
Installation
1 . Be sure all electrical disconnects are open and tagged before any work begins. Inspect the package contents for any damage during shipping. File a claim with the shipper if damage has occurred.
2.For ease of installation,
3. | Install the additional unloader cylinder head on the lead | |
| compressor, Al or El, according to instructions pro- | |
| vided by the compressor manufacturer in the accessory | |
| package. | |
4. | Continue installation per either | |
1 | units or 130 (50 Hz), | |
section as appropriate. | ||
|
0
1 . Wire the solenoid before any field wiring begins. Wir- ing between components and control box must be en- closed in conduit. All local electrical codes and National Electrical Code (NEC) must be followed. Factory wires are provided in the compressor harness to connect the solenoid. These wires are in the compressor control box.
2.Wire the control side. Open the left side control box door and remove inner panel. Using the holes provided and
Wire the primary side of the transformer in parallel with TRAN3. See Fig. 23. This supplies transformer with proper line voltage. Be sure to connect proper tap of the trans- former to ensure supply of proper secondary voltage.
Wire the secondary side of transformer to
3.When all connections are made, check for proper wiring and tight connections. Replace and secure inner panel. Restore power to unit.
4.Configure the processor. With the addition of extra un- loaders, the unit configuration has changed. To change the configuration of the processor, enter the service func- tion using the keypad and display module. Before any changes can be made, the
a. | Press pJl,,,l* Keypad | LCD displays the | word | ||
|
|
|
|
|
|
| PASSWORD. |
|
| ||
b, | Enter md riim ms [;;;;;I | . p K e y pl a d LCDa y | s | ||
|
|
|
|
| |
| LOGGEDON. |
|
|
C.To change configuration, press m H. Keypad LCD displays FLD CFG.
d. If an additional unloader was added to compressor Al, press m until NULA 1 appears in keypad dis-
play. Press mf o r Fit h e n u m b e r o f u n l o a d e r s o n circuit A. Keypad display now reads NULA 2.
If an additional unloader was added to compressor B 1, press q until NULB 1 appears in keypad dis-
play. Press m bi for the number of unloaders on circuit B. Keypad display now reads NULB 2.
When configuration is complete, press mM. Key- pad display reads LOGGEDON. Press m until key-
pad display reads LOG OFF. Press H . Keypad dis-
play reads EXIT LOG.
III
5.Using test function, check unloaders. Press 12 1pEsTI. Key- pad display reads OUTPUTS. Press I)I until display
reads ULA 2 OFF. Press q . Relay energizes. Press a and relay deenergizes. Press Li_] until display reads
ULB2 OFF. Press H . Relay energizes. Press q and relay deenergizes.
6. When unloader check has been performed, return LOCAL/
68