scribed in m H and r;lFl sections on page 38.

8.Reinstall all 6 wire connectors and the green ground wire.

9.Carefully check all wiring connections before restoring power.

10.Verify the LOCAL/ENABLE-STOP-CCN switch is in STOP position

11.Restore control power. Verify the red and green lights on top of PSI0 and front of each DSIO module re- spond as described in Control Modules section on page 64. The keypad and display module @IS10 or LID) should also begin its rotating display.

12.Using the keypad and display module, press [p-&q,to verify that the software version number matches the ER (engineering requirement) number shown on the PSI0 label.

13.Press [qnSRVC to verify that the 6 factory configuration

codes (CODE 1 through CODE 6) exactly match the codes listed for this unit model on the component ar- rangement label diagram on the control box door. If they are different or are all zeros, reenter the 6 codes. If any changes are required, the PSI0 display becomes

blank and reconfigures itself after pressing the H key

while displaying CODE 6. The display returns in ap- proximately 15 seconds.

NOTE: Codes with leading zeros in the configuration will be displayed starting with the first number greater than zero.

14.Press nn4 sRvc to verify each item is configured as needed

for this particular installation. Table 9 shows the fac- tory configuration code default settings. Table 9 also shows the service replacement code default settings which are used if no model number was specified when or- dering the replacement PSI0 module. It is strongly sug-

gested that the Start-Up Checklist for Flotronic’” II Chiller Systems (completed at time of original start-up) be used at this time to verify and/or reprogram the various op- tions and configurations required for this job.

15.After completing the configuration steps outlined above, restore main power and perform a unit test as de-

scribed in m H and r;lFl sections on page 38.

16, Complete this procedure and restore chiller to normal operation by returning the LOCAL/ENABLE-STOP- CCN switch to desired position.