Table 3 — 50VQP Unit Electrical Data — Standard Unit

50VQP UNIT

VOLTAGE

MIN/MAX

BLOWER

 

COMPRESSOR

FAN

TOTAL UNIT

 

MAX FUSE/

 

 

 

 

MOTOR

MCA

SIZE

(V-Ph-Hz)

VOLTAGE

OPTION

qty

 

RLA

LRA

FLA

HACR

 

FLA

 

 

 

 

 

 

 

 

 

 

 

 

084

380/420-3-50

360/440

A,B,C

1

 

11.2

75.0

1.8

13.0

15.8

25

E

1

 

11.2

75.0

2.5

13.7

16.5

25

 

 

 

 

096

380/420-3-50

360/440

A,B,C

1

 

12.2

101.0

2.5

14.7

17.8

25

120

380/420-3-50

360/440

A,B,C

1

 

16.7

111.0

3.6

20.3

24.5

40

E

1

 

16.7

111.0

4.9

21.6

25.8

40

 

 

 

 

150

380/420-3-50

360/440

A,B,C

1

 

18.6

118.0

4.9

23.5

28.2

45

E

1

 

18.6

118.0

7.8

26.4

31.1

45

 

 

 

 

168

380/420-3-50

360/440

A,B,C

2

 

11.2

75.0

3.4

25.8

28.6

35

192

380/420-3-50

360/440

A,B,C

2

 

12.2

101.0

4.9

29.3

32.3

40

240

380/420-3-50

360/440

A,B,C

2

 

16.7

111.0

7.8

41.2

45.4

60

300

380/420-3-50

360/440

A,B,C

2

 

18.6

118.0

7.8

45.0

49.7

60

E

2

 

18.6

118.0

12.2

49.4

54.0

70

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning, and Refrigeration

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

RLA — Rated Load Amps

NOTES:

1.HACR circuit breaker in U.S.A. only.

2.All fuses Class RK-5.

Table 4 — 50VQP Unit Electrical Data — Dual Point Power Unit

50VQP

VOLTAGE

MIN/MAX

BLOWER

 

 

 

COMPRESSOR

 

EMERGENCY POWER SUPPLY

UNIT

(V-Ph-Hz)

VOLTAGE

OPTION

qty

RLA

LRA

TOTAL

COMP

COMP

FAN MOTOR

FAN

FAN

SIZE

 

COMP FLA

MCA

MAX FUSE

FLA

MCA

MAX FUSE

 

 

 

 

 

 

 

084

 

380/420-3-50

360/440

A,B,C

1

11.2

75.0

11.2

14.0

25

1.8

2.3

15

 

E

1

11.2

75.0

11.2

14.0

25

2.5

3.1

15

 

 

 

 

096

 

380/420-3-50

360/440

A,B,C

1

12.2

101.0

12.2

15.3

25

2.5

3.1

15

120

 

380/420-3-50

360/440

A,B,C

1

16.7

111.0

16.7

20.9

35

3.6

4.5

15

 

E

1

16.7

111.0

16.7

20.9

35

4.9

6.1

15

 

 

 

 

150

 

380/420-3-50

360/440

A,B,C

1

18.6

118.0

18.6

23.3

40

4.9

6.1

15

 

E

1

18.6

118.0

18.6

23.3

40

7.8

9.8

15

 

 

 

 

168

 

380/420-3-50

360/440

A,B,C

2

11.2

75.0

22.4

25.2

35

3.4

4.3

15

192

 

380/420-3-50

360/440

A,B,C

2

12.2

101.0

24.4

27.4

35

4.9

6.1

15

240

 

380/420-3-50

360/440

A,B,C

2

16.7

111.0

33.4

37.6

50

7.8

9.8

15

300

 

380/420-3-50

360/440

A,B,C

2

18.6

118.0

37.2

41.9

60

7.8

9.8

15

 

E

2

18.6

118.0

37.2

41.9

60

12.2

15.3

25

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

FLA — Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

HACR — Heating, Air Conditioning, and Refrigeration

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

NOTES:

1.HACR circuit breaker in U.S.A. only.

2.All fuses Class RK-5.

16

Page 16
Image 16
Carrier 50VQP084-300 50VQP Unit Electrical Data Standard Unit, 50VQP Unit Electrical Data Dual Point Power Unit