Table 7 — 50VQP120 Blower Performance Data (cont)

 

AIRFLOW

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (Pa)

 

 

 

 

 

 

 

 

 

(l/s)

0

 

25

50

75

100

125

 

150

175

200

225

 

250

275

300

325

350

375

 

 

 

BkW

0.55

 

0.63

0.67

0.70

0.78

0.82

 

0.85

0.93

1.00

1.04

 

1.08

1.15

1.19

1.23

1.30

1699.2

 

Sheave/Mtr

A

 

A

A

A

A

A

 

C

C

C

C

 

C

C

C

C

C

 

RPM

511

 

544

578

608

637

668

 

695

722

748

776

 

800

825

849

874

897

 

 

 

 

 

 

 

 

 

Turns Open

6

 

5

3.5

3

2

1

 

6

5

4.5

3.5

 

3

2

1.5

0.5

0

 

 

 

BkW

0.63

 

0.67

0.70

0.78

0.85

0.89

 

0.93

1.00

1.04

1.08

 

1.15

1.23

1.26

1.30

1746.4

 

Sheave/Mtr

A

 

A

A

A

A

A

 

C

C

C

C

 

C

C

C

C

 

RPM

526

 

561

592

621

649

679

 

706

732

758

785

 

809

833

857

882

 

 

 

 

 

 

 

 

 

Turns Open

5.5

 

4.5

3.5

2.5

1.5

1

 

5.5

5

4

3.5

 

2.5

2

1

0.5

 

 

 

BkW

0.67

 

0.70

0.78

0.82

0.85

0.93

 

1.00

1.04

1.08

1.15

 

1.23

1.26

1.30

1.38

1793.6

 

Sheave/Mtr

A

 

A

A

A

A

C

 

C

C

C

C

 

C

C

C

C

 

RPM

544

 

575

605

633

661

691

 

717

742

767

794

 

818

842

867

890

 

 

 

 

 

 

 

 

 

Turns Open

5

 

4

3

2

1

6

 

5.5

4.5

4

3

 

2

1.5

0.5

0

 

 

 

BkW

0.70

 

0.78

0.85

0.89

0.93

1.00

 

1.08

1.11

1.15

1.23

 

1.30

1.34

1.38

1.45

1840.8

 

Sheave/Mtr

A

 

A

A

A

A

C

 

C

C

C

C

 

C

C

C

E

 

RPM

555

 

589

618

646

676

702

 

728

753

779

803

 

827

850

875

898

 

 

 

 

 

 

 

 

 

Turns Open

4.5

 

3.5

2.5

1.5

6

6

 

5

4

3.5

2.5

 

2

1

0.5

0

 

 

 

BkW

0.78

 

0.82

0.85

0.93

1.00

1.08

 

1.11

1.15

1.23

1.30

 

1.34

1.38

1.50

1.53

1888.0

 

Sheave/Mtr

A

 

A

A

A

C

C

 

C

C

C

C

 

C

C

E

E

 

RPM

572

 

601

630

657

686

712

 

737

762

789

812

 

836

859

883

905

 

 

 

 

 

 

 

 

 

Turns Open

4

 

3

2

1

6

5.5

 

4.5

4

3

2.5

 

1.5

1

0

0

 

 

 

BkW

0.85

 

0.89

0.93

1.00

1.08

1.11

 

1.15

1.23

1.30

1.38

 

1.41

1.50

1.53

1935.2

 

Sheave/Mtr

A

 

A

A

A

C

C

 

C

C

C

C

 

C

E

E

 

RPM

589

 

617

645

672

700

726

 

751

775

801

824

 

847

872

894

 

 

 

 

 

 

 

 

 

Turns Open

3.5

 

2.5

1.5

1

6

5

 

4.5

3.5

2.5

2

 

1

0.5

0

 

 

 

BkW

0.93

 

0.96

1.00

1.08

1.15

1.19

 

1.23

1.30

1.38

1.50

 

1.53

1.56

1982.4

 

Sheave/Mtr

A

 

A

A

C

C

C

 

C

C

C

E

 

E

E

 

RPM

605

 

633

660

689

714

739

 

763

790

813

836

 

858

882

 

 

 

 

 

 

 

 

 

Turns Open

3

 

2

1

6

5.5

4.5

 

4

3

2

1.5

 

1

0.5

 

 

 

BkW

0.96

 

1.00

1.08

1.15

1.23

1.26

 

1.30

1.38

1.50

1.53

 

1.60

1.68

2029.6

 

Sheave/Mtr

A

 

A

A

C

C

C

 

C

C

E

E

 

E

E

 

RPM

621

 

649

675

703

728

752

 

776

802

827

847

 

869

893

 

 

 

 

 

 

 

 

 

Turns Open

2.5

 

1.5

1

6

5

4

 

3.5

2.5

2

1.5

 

1

0

 

 

 

BkW

1.040

 

1.08

1.15

1.23

1.30

1.38

 

1.41

1.50

1.53

1.60

 

1.68

1.75

2076.8

 

Sheave/Mtr

A

 

A

C

C

C

C

 

C

E

C

E

 

E

E

 

RPM

637

 

664

690

717

742

766

 

791

814

836

858

 

882

904

 

 

 

 

 

 

 

 

 

Turns Open

2

 

1

6

5.5

4.5

4

 

3

2

2

1

 

0.5

0

 

 

 

BkW

1.11

 

1.15

1.23

1.30

1.38

1.45

 

1.53

1.56

1.60

1.68

 

1.75

2124.0

 

Sheave/Mtr

A

 

A

C

C

C

C

 

E

E

C

E

 

E

 

RPM

653

 

679

707

731

755

779

 

804

826

848

870

 

893

 

 

 

 

 

 

 

 

 

Turns Open

1.5

 

1

5.5

5

4

3.5

 

3

2

1.5

1

 

0

 

 

 

BkW

0.96

 

1.00

1.08

1.15

1.23

1.26

 

1.30

1.38

1.50

1.53

 

1.60

1.68

2029.6

 

Sheave/Mtr

A

 

A

A

C

C

C

 

C

C

E

E

 

E

E

 

RPM

621

 

649

675

703

728

752

 

776

802

827

847

 

869

893

 

 

 

 

 

 

 

 

 

Turns Open

2.5

 

1.5

1

6

5

4

 

3.5

2.5

2

1.5

 

1

0

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

A

Standard rpm/Standard Motor

 

 

 

 

 

 

 

1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open.

 

 

 

 

 

 

 

Other speeds require field selection.

 

 

 

 

B

Low rpm/Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. For applications requiring higher static pressures, contact your local Carrier rep-

bhp

Brake Horsepower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resentative. Performance data does not include drive losses and is based on sea

C

High rpm/Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

level conditions.

 

 

 

 

 

 

E

High rpm/Large Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on

ESP

External Static Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lowest voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High

Rpm/Standard Motor, E = High Rpm/Large Motor.

23

Page 23
Image 23
Carrier 50VQP084-300 specifications 511 544 578 608 637 668 695 722 748 776 800 825 849 874 897, 040