Table 10 — 50VQP192 Blower Performance Data (cont)

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (Pa)

 

 

 

 

 

 

 

(l/s)

0

25

50

75

100

125

 

150

175

200

225

 

250

275

300

325

350

375

 

BkW

0.66

0.79

0.88

0.96

1.03

1.11

 

1.26

1.33

1.41

1.48

 

1.56

2926.4

Sheave/Mtr

B

B

B

A

A

A

 

A

A

C

C

 

C

RPM

421

459

499

533

569

600

 

633

663

691

722

 

749

 

 

 

 

Turns Open

4.5

3.5

2

5

4

3

 

2

1

2.5

2

 

1.5

 

BkW

0.73

0.81

0.96

1.03

1.11

1.26

 

1.33

1.41

1.48

1.56

 

1.71

3020.8

Sheave/Mtr

B

B

A

A

A

A

 

A

C

C

C

 

C

RPM

441

478

513

549

581

614

 

644

672

703

730

 

759

 

 

 

 

Turns Open

4

2.5

6

4.5

3.5

3

 

1.5

3.5

2.5

2

 

1

 

BkW

0.81

0.96

1.03

1.11

1.24

1.33

 

1.41

1.48

1.56

1.71

 

1.84

3115.2

Sheave/Mtr

B

B

A

A

A

A

 

A

C

C

C

 

C

RPM

456

495

529

561

595

625

 

656

685

712

741

 

767

 

 

 

 

Turns Open

3.5

2

5.5

4

3

2.5

 

1

3.5

2.5

2

 

1

 

BkW

0.94

1.03

1.11

1.18

1.26

1.41

 

1.48

1.56

1.71

1.78

 

1.86

3209.6

Sheave/Mtr

B

A

A

A

A

A

 

A

C

C

C

 

C

RPM

471

506

539

574

604

633

 

664

692

721

747

 

773

 

 

 

 

Turns Open

3

6

5

3.5

3

2

 

1

3

2

2

 

1

 

BkW

0.96

1.11

1.18

1.26

1.41

1.48

 

1.56

1.71

1.84

1.93

 

3304.0

Sheave/Mtr

B

A

A

A

A

A

 

A

C

C

C

 

RPM

486

520

555

586

615

647

 

674

704

730

756

 

 

 

 

 

Turns Open

2.5

5.5

4.5

3

2.5

1.5

 

1

3

2

1.5

 

LEGEND

AStandard rpm/Standard Motor

BLow rpm/Standard Motor bhp — Brake Horsepower

CHigh rpm/Standard Motor ESP — External Static Pressure

NOTES:

1.Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection.

2.For applications requiring higher static pressures, contact your local Carrier repre- sentative. Performance data does not include drive losses and is based on sea level conditions.

3.All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on lowest voltage.

4.A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High Rpm/ Standard Motor.

28

Page 28
Image 28
Carrier 50VQP084-300 specifications BkW 3020.8 Sheave/Mtr