38
Table 20 — Complete C Control Current LED Status and Alarm Relay Operations
LEGEND
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by
a 10-second pause. This sequence will repeat continually until the fault is
cleared.
Table 21 — Complete C Control LED Code andFault Descriptions
LEGEND
Table 22 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
LEGEND NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by
a 10-second pause. This sequence will repeat continually until the fault is
cleared.
LED STATUS DESCRIPTION OF OPERATION ALARM RELAY
On
Normal Mode Open
Normal Mode with
PM Warning
Cycle
(closed 5 sec.,
Open 25 sec.)
Off Complete C Control is
non-functional Open
Slow Flash
Fault Retry Open
Over/Under Voltage Shutdown
Open
(Closed after
15 minutes)
Fast Flash Lockout Closed
Flashing Code 1 Test Mode — No fault in memory Cycling Code 1
Flashing Code 2 Test Mode — HP Fault in memory Cycling Code 2
Flashing Code 3 Test Mode — LP Fault in memory Cycling Code 3
Flashing Code 4 Test Mode — FP1 Fault in memory Cycling Code 4
Flashing Code 5 Test Mode — FP2 Fault in memory Cycling Code 5
Flashing Code 6 Test Mode — CO Fault in memory Cycling Code 6
Flashing Code 7 Test Mode — Over/Under
shutdown in memory Cycling Code 7
Flashing Code 8 Test Mode — PM in memory Cycling Code 8
Flashing Code 9 Test Mode — FP1/FP2
Swapped fault in memory Cycling Code 9
CO Condensate Overflow
FP Freeze Protection
HP High Pressure
LED — Light-Emitting Diode
LP Low Pressure
PM — Performance Monitor
LED
CODE FAULT DESCRIPTION
1No fault in memory There has been no fault since the
last power-down to power-up
sequence
2High-Pressure
Switch
HP Open Instantly
3Low-Pressure Switch LP open for 30 continuous seconds
before or during a call (bypassed for
first 60 seconds)
4Freeze Protection
Coax — FP1
FP1 below Temp limit for 30 continu-
ous seconds (bypassed for first 60
seconds of operation)
5Freeze Protection Air
Coil — FP2
FP2 below Temp limit for 30 continu-
ous seconds (bypassed for first 60
seconds of operation)
6Condensate overflow Sense overflow (grounded) for 30
continuous seconds
7
(Autoreset)
Over/Under Voltage
Shutdown
"R" power supply is <19VAC or
>30VAC
8PM Warning Performance Monitor Warning has
occurred.
9FP1 and FP2 Therm-
istors are swapped
FP1 temperature is higher than FP2
in heating/test mode, or FP2 temper-
ature is higher than FP1 in cooling/
test mode.
FP Freeze Protection
HP High Pressure
LED — Light-Emitting Diode
PM — Performance Monitor
DESCRIPTION STATUS LED
(Green)
TEST LED
(Yellow) FAULT LED (Red) ALARM RELAY
Normal Mode On Off Flash Last Fault Code in Memory Open
Normal Mode with PM On Off Flashing Code 8 Cycle (closed 5 sec,
open 25 sec, …)
Deluxe D Control is
non-functional Off Off Off Open
Test Mode On Flash Last Fault Code in Memory Cycling Appropriate Code
Night Setback Flashing Code 2 Flash Last Fault Code in Memory
ESD Flashing Code 3 Flash Last Fault Code in Memory
Invalid T-stat Inputs Flashing Code 4 Flash Last Fault Code in Memory
No Fault in Memory On Off Flashing Code 1 Open
HP Fault Slow Flash Off Flashing Code 2 Open
LP Fault Slow Flash Off Flashing Code 3 Open
FP1 Fault Slow Flash Off Flashing Code 4 Open
FP2 Fault Slow Flash Off Flashing Code 5 Open
CO Fault Slow Flash Off Flashing Code 6 Open
Over/Under Voltage Slow Flash Off Flashing Code 7 Open (closed after 15 minutes)
HP Lockout Fast Flash Off Flashing Code 2 Closed
LP Lockout Fast Flash Off Flashing Code 3 Closed
FP1 Lockout Fast Flash Off Flashing Code 4 Closed
FP2 Lockout Fast Flash Off Flashing Code 5 Closed
CO Lockout Fast Flash Off Flashing Code 6 Closed
CO Condensate Overflow
ESD — Emergency Shutdown
FP Freeze Protection
HP High Pressure
LP Low Pressure
PM Performance Monitor