Carrier 48MPD Ð Optional VFD Ð Wiring Connections, Ð CCN Connection Approved Shielded Cables

Models: MPE62L-10R 50MP62L-10R 48MPD

1 64
Download 64 pages 9.38 Kb
Page 23
Image 23
Fig. 29 Ð Optional VFD Ð Wiring Connections

 

 

 

VFD

PECB (EXHAUST)

PEC (EXHAUST)

 

 

IFCB (SUPPLY)

IFC (SUPPLY)

 

 

L1

L1

(R)

T1

L2

L2 (S)

T2

L3

L3

(T)

T3

 

460V

 

SHIELD

 

G

 

VOLTAGE

(SUPPLY)

SELECTOR

 

PSIO1

 

J6

S1

CHANNEL 16

+ 46

FI

- 47

FC

 

SC

(EXHAUST)

PSIO1

J6

CHANNEL 15

+43

-44

EFM (EXHAUST)

IDFM (SUPPLY)

GROUND

 

1

 

IFR (SUPPLY

 

PER (EXHAUST)

 

3

 

LEGEND

EFM

Ð Exhaust Fan Motor

IDFM

Ð Indoor Fan Motor

IFC

Ð Indoor Fan Contactor

IFCB

Ð Indoor Fan Circuit Breaker

IFR

Ð Indoor Fan Relay

PEC

Ð Power Exhaust Contactor

PECB Ð Power Exhaust Circuit Breaker

PER

Ð Power Exhaust Relay

VFD

Ð Variable Frequency Drive

Fig. 29 Ð Optional VFD Ð Wiring Connections

Carrier Comfort Network Interface Ð The 48/50MP units can be connected to the CCN if desired. The communication bus wiring is supplied and installed in the ®eld. It consists of shielded, 3-conductor cable with drain wire.

The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it, the negative pins must be wired to the negative pins, and the signal pins must be wired to signal ground pins. Wiring con- nections for CCN should be made at the 4-pin plug (COMM) located at the bottom right side of the fuse bracket in the main control box. Consult CCN Contractor's Manual for fur- ther information.

NOTE: Conductors and drain wire must be 20 AWG mini- mum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Te¯on, or poly- ethylene. An aluminum/polyester 100% foil shield and an

outer jacket of PVC, PVC/nylon, chrome vinyl, or Te¯on with a minimum operating temperature range of 220 C to 60 C is required. See Table 7 for cables that meet the requirements.

Table 7 Ð CCN Connection Approved

Shielded Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

 

 

IMPORTANT: When connecting the CCN communi- cation bus to a system element, use a color coding sys- tem for the entire network to simplify installation and checkout.

23

Page 23
Image 23
Carrier 48MPD, MPE62L-10R, 50MP62L-10R Ð Optional VFD Ð Wiring Connections, Ð CCN Connection Approved Shielded Cables