If the unit is being used in a CV application, then perform the following:
1.Enter the con®guration function by pressing and
.
2.Scroll down to unit type. TYPE 1 will be displayed.
3.Press and ENTER to change the unit type to CV.
4.Scroll down to data reset. DTRS will be displayed. Press
and ENTER to save changes.
The fan operation type should also be con®gured for use in occupied time periods. Fan operation can be
set to continuous or auto. To set, press to enter the subfunction. Scroll down to fan mode (FANM). Press
and | ENTER | to set to AUTO. Press | and | ENTER | to set |
to continuous. |
|
|
|
ENTER JOB SET POINT VALUES Ð The set point func- tion allows the user to view the current values set for the unit. From this function, the user can change the values.
Reading and Changing Set Points Ð To change the set point of a particular feature, enter the appropriate subfunction and scroll to the variable desired. Once the desired variable has
been reached, type in the new value and press ENTER . The new value will appear in the display.
For example, the occupied cool set point is currently set at the default value of 78 F. To change the occupied set point to 72 F:
1.Press to enter the occupied cool set point function. The display will read OCSP 78.
2.Press ENTER and the display will read OCSP 72.
Set points can be changed by the user provided that the values are within the allowable range for the input. If the input is not within the allowable range, the original value will remain displayed. See Table 24 for allowable ranges and default values.
To change the demand limit set points, the functions must ®rst be enabled in the ®eld con®guration subfunction.
CONFIGURE UNIT CONTROLS AND FUNCTIONS Ð Refer to Table 25 for a suggested sequence for entering Basic System Con®guration data. These values may be changed from the HSIO at any time. If changing default values via the CCN, the 48/50MP unit must ®rst be in run mode (STBY NO).
NOTE: After changing any of the values in the con®guration group, enable the Data Reset function.
QUICK TEST FUNCTION Ð Enable and run the Quick Test function. Refer to the Controls and Troubleshooting manual for more information on Quick Test.
Table 24 Ð Set Point Ranges and Defaults
| DISPLAY |
| SET POINT | DEFAULT | ALLOWABLE |
|
| DESCRIPTION | VALUE | RANGE | |
|
|
| |||
| BPSP |
| Building pressure set point | 0.05 in. wg | 0 to .50 in. wg |
| ECSO* |
| Economizer set point offset | 3 | 1 to 10 |
| HHL²/HHOR* |
| High humidity override (percent) | 99% | 0 to 100% |
| HTMP |
| High temperature minimum position | 35 F | 0 to 100 F |
| HUSP |
| Humidity set point (percent)** | 40% | 0 to 100% |
| IAQS² |
| IAQ set point | 650 ppm | 0 to 2000 ppm |
| LIMT² |
| Reset limit (F) | 10 F | 0 to 20 F |
| LSP |
| Loadshed set point (percent) | 50% | 0 to 100% |
| LTMP |
| Low temperature minimum position | 10 F | 0 to 100 F |
| MDP² |
| Minimum damper position (percent) | 20% | 0 to 100% |
| NTLO² |
| NTFC lockout temperature (F) | 50 F | 40 to 70 F |
| OLS²/OACS* |
| 1 cfm | 0 to 50,000 cfm | |
| OCSP |
| Occupied cool set point (F)** | 78 F | 55 to 80 F |
| OHSP |
| Occupied heat set point (F)** | 68 F | 55 to 80 F |
| PES² |
| Power exhaust on set point (percent) | 90% | 30 to 100% |
| RTIO² |
| Reset ratio (F) | 3 F | 0 to 10 F |
| SASP |
| Supply air set point (F) | 55 F | 45 to 70 F |
| SPSP |
| Static pressure set point²² | 1.5 in. wg | 0 to 5.0 in. wg |
| UCDB* |
| Unoccupied cooling deadband | 1 | 0 to 10 |
| UCSP |
| Unoccupied cool set point (F)** | 90 F | 75 to 95 F |
| UHDB* |
| Unoccupied heating deadband | 1 | 0 to 10 |
| UHSP |
| Unoccupied heat set point (F)** | 55 F | 40 to 80 F |
|
|
|
|
|
|
| LEGEND |
|
|
| |
IAQ | Ð |
|
|
| |
NFTC | Ð Unoccupied Free Cooling |
|
|
| |
ppm | Ð Parts Per Million |
|
|
|
*These items are found under the Service function, and can only be accessed using either the Build- ing Supervisor or Service Tool.
²These items are found under the Service function. **Occupied space.
²²Supply duct.
NOTE: Set points HHL/HHOR and OCS/OACS are displayed differently on the HSIO and Building Su- pervisor. The set points are shown as HHL and OCS on the HSIO. The set points are shown as HHOR and OACS on Building Supervisor or Service Tool.