Carrier 50MP62L-10R, 48MPD Pre-Start-Up, System Check, Ð Compressor Mounting Ð 48/50MP62L Units

Models: MPE62L-10R 50MP62L-10R 48MPD

1 64
Download 64 pages 9.38 Kb
Page 28
Image 28
Fig. 41 Ð Compressor Mounting Ð

Fig. 41 Ð Compressor Mounting Ð

48/50MP62L Units

Fig. 42 Ð Front View of Compressor Mounting

Rail Assembly Ð 48/50MP70M-10R Units

COMPRESSOR MOUNTING FOOT

NUT Fig. 42 Ð Front View of Compressor MountingRail Assembly Ð 48/50MP70M-10R Units

COMPRESSOR MOUNTING RAIL

Fig. 43 Ð Rear View of Compressor Mounting

Rail Assembly Ð 48/50MP70M-10R Units

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up or Start- Up, review Start-Up Checklist at the center of this publication. The Checklist assures proper start-up of a unit and provides a record of unit condition, applica- tion requirements, system information, and operation at initial start-up.

Do not attempt to start the air-conditioning system until following checks have been completed.

System Check

1.Check the outside air hoods to ensure the hoods are fully opened and secure, with ®lters in place.

2.Check the supply fan and exhaust fan suspension brack- ets. Shipping spacers should be removed and sleds levelled to speci®cation.

3.Check compressor suspension. On 48/50MP62L units snubber washers can be moved with ®nger pressure. On all other units, rails allow compressors to ¯oat freely on compressor rail springs.

4.Electrical power source must agree with unit nameplate.

5.Check tightness of all electrical connections.

Failure to open discharge service valve prior to start- ing compressor can result in damage to or failure of the compressor.

6.Backseat (open) compressor suction and discharge shut- off valves. Close valves one turn to allow refrigerant pres- sure to reach the test gages.

7.Open liquid line service valves.

8.Oil should be visible in the compressor sight glasses. See Fig. 44. An acceptable oil level in the compressor is from 3¤8 to 1¤8 of sight glass (06E-299 compressors are 1¤8 of sight glass). Adjust the oil level as required. No oil should be removed unless the crankcase heater has been energized for at least 24 hours. Oil Charge section on page 49 for Carrier-approved oils.

9.Perform leak test. Be sure there are no refrigerant leaks. All units are shipped with a complete operating charge of R-22 and should be under sufficient pressure for leak testing after installation. If there is no system pressure, add refrigerant until a pressure is observed and check for leaks. After leaks are repaired, remove and recover refrigerant from system. For leak testing procedures, see GTAC 2, Module 5, Charging, Recovery, Recycling and Reclamation section. Do not use the system compres- sors to remove refrigerant from the system.

10.Crankcase heaters must be ®rmly locked into compres- sors, and must be on for 24 hours prior to start-up.

Crankcase heaters on all units are wired into the control circuit, so they are always operable as long as the main power supply disconnect is on (closed), even if any safety device is open. Compressor heat- ers must be on for 24 hours prior to the start-up of any compressor.

28

Page 28
Image 28
Carrier 50MP62L-10R, MPE62L-10R, 48MPD specifications Pre-Start-Up, System Check, Ð Compressor Mounting Ð 48/50MP62L Units