CONDENSER-FAN MOTOR PROTECTION Ð Each condenser-fan motor is internally protected against over- temperature. They are also protected against a severe over- current condition by manual reset, calibrated trip, magnetic circuit breakers on a common circuit. As with the circuit break- ers, do not bypass connections or increase breaker size to correct trouble. Determine the cause and correct it before resetting the breaker.

HIGH- AND LOW-PRESSURE SWITCHES Ð See Fig. 60 for compressor mounting locations. Settings for these switches are shown in Table 33. If either switch trips, that refrigerant circuit will be automatically locked out by the controls. To reset, interrupt control power.

NOTE: When a pressure transducer is used, the low pres- sure trip point is the same as the low-pressure switch.

Variable Frequency Drive (VFD)

SUPPLY FAN VFD Ð The optional supply fan VFD is lo- cated in the auxiliary control box. Wiring should only be performed by quali®ed personnel. All parameters have been factory set. Do not change parameters unless necessary.

The VFD can be easily damaged by static electricity. Use proper electrostatic discharge procedures when handling the controls of the VFD.

Never connect main circuit output terminals T1, T2, and T3 to AC main circuit power supply. Always ground the VFD using the designated ground terminal. Refer to the VFD tech- nical manual for more information.

The VFD can indicate faults and alarms. A blinking alarm condition is a warning that a trouble condition will occur or that there is a problem in the external circuitry. The VFD will continue to operate during an alarm condition. Alarm conditions are not entered into the fault register.

A steady fault indicator is displayed when the VFD fault relay has tripped. The motor will coast to a stop, and a fault signal is output is present.

Refer to the VFD technical manual for more information on alarms and faults.

EXHAUST FAN VFD Ð The optional exhaust fan VFD con- sists of an exhaust fan, motor, VFD, and pressure transducer. All components (except the tranducer) are located in the re- turn air section of the 48/50MP, through the hinged access door. The BP transducer is located in the auxiliary control box. Wiring should only be performed by quali®ed person- nel. All parameters have been factory set. Do not change pa- rameters unless necessary.

The VFD can be easily damaged by static electricity. Use proper electrostatic discharge procedures when handling the controls of the VFD.

Never connect main circuit output terminals T1, T2, and T3 to AC main circuit power supply. Always ground the VFD using the designated ground terminal. Refer to the VFD tech- nical manual for more information.

The VFD can indicate faults and alarms. A blinking alarm condition is a warning that a trouble condition will occur or that there is a problem in the external circuitry. The VFD will continue to operate during an alarm condition. Alarm conditions are not entered into the fault register.

A steady fault indicator is displayed when the VFD fault relay has tripped. The motor will coast to a stop, and a fault signal is output is present.

Refer to the VFD technical manual for more information on alarms and faults.

DISPLAYING FAULT SEQUENCE Ð Whenever the fault relay trips and shuts down the VFD, the display code of the

fault that caused the trip will be displayed until RESET is

pressed. The fault code will also be entered into the fault register. The register retains, in sequence, the last 3 fault codes. A newly occurring fault code will not change the fault reg- ister if it a recurrence of the most recently entered fault. The contents of the register can be displayed by performing the following steps:

1.Press DSPL until the MONTR LED is on.

2.Press until U-09 is displayed.

3.Press ENTER . The current fault code will be displayed.

4.Press . The display will indicate that this is the ®rst code in the memory register.

5.Continue to press to display the other codes in the fault resister. After the last code has been displayed, the sequence will return to the ®rst code.

Control Modules Ð The standard PSIO1 and optional PSIO2 (processor modules) and standard DSIO1 and DSIO2 (high-voltage relay modules) all perform continuous diag- nostic evaluations of the hardware condition. Proper opera- tion of these modules is indicated by 2 light-emitting diodes (LED) on the front surface of the DSIO modules and on the top horizontal surface of the PSIO modules.

RED LED Ð Blinking continuously at a 3 to 5 second rate indicates proper operation. Lit continuously indicates a prob- lem requiring replacement of the module. Off continuously indicates the power supply should be checked. If there is no input power, check the fuses. If a fuse is bad, check for shorted secondary of the transformer or a bad module.

GREEN LED Ð On a PSIO module, this is the green light that is closest to the COMM connectors. The other green LED on the module indicates external communications (when used). The green LED should always be blinking when power is on. It indicates that the modules are communicating prop- erly. If the green LED is not blinking, check the red LED. If the red LED is normal, check the module addresses.

NOTE: If the wrong address is entered for the DSIO1 and 2 and/or PSIO1 and 2, then the wrong input channel will be read and the wrong output channel energized.

If all modules indicate a communication failure, check the COMM plug on the PSIO module for proper seating. If a good connection is made and the condition persists, replace the PSIO module.

If only the DSIO module indicates a communication fail- ure, check the COMM plug on that module for a proper con- nection. If a good connection is made and the condition persists, replace the DSIO module.

All system operating intelligence resides in the PSIO mod- ule. This module monitors conditions through the input and output ports and the DSIO modules.

The machine operator communicates with the micro- processor through the HSIO keypad and display module. Com- munication between the PSIO and the other modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module.

On the sensor bus terminal strips, terminal 1 of the PSIO1 module is connected to Terminal 1 of all of the other mod- ules. Terminals 2 and 3 are connected in the same manner. If any of the wires are crossed, the system will not work.

The unit processor modules, the high-voltage relay mod- ules, and the HSIO keypad module are all powered from two 21-vac power sources which connect to terminals 1 and 2 of the power input strip on each module.

53

Page 53
Image 53
Carrier 48MPD, MPE62L-10R, 50MP62L-10R specifications Variable Frequency Drive VFD

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.