Table 18 Ð Component Pressure Drop (in. wg)
COMPONENT | 22,000 | 26,400 | 30,000 | 34,000 | 38,000 | 42,000 | 45,800 | 48,200 | 52,000 | |
HEAT EXCHANGER | 0.31 | 0.40 | 0.49 | 0.58 | 0.70 | 0.82 | 0.95 | 1.03 | 1.23 | |
(48MP ONLY) | ||||||||||
|
|
|
|
|
|
|
|
|
Table 19 Ð Maximum Allowable
Supply Fan Wheel Speed (Rpm)
48/50MP | FAN TYPE |
| |
Forward Curved |
| Airfoil | |
|
| ||
62L, 70M | 835 |
| 1595 |
82N, 90P, 10R | 715 |
| 1298 |
|
|
|
|
Table 20 Ð Maximum Allowable Power Exhaust
Fan Speed (Rpm)
48/50MP |
| FAN TYPE | |
50% Air |
| 100% Air | |
|
| ||
62L, 70M | 690 |
| 650 |
82N, 90P, 10R | 600 |
| 560 |
|
|
|
|
Table 21 Ð Air Quantity Limits (cfm)
|
|
| MINIMUM | MINIMUM |
UNIT |
|
| GAS HEATING | GAS HEATING |
SIZE | MINIMUM | MAXIMUM | (Low Heat | (High Heat |
48/50MP |
|
| Units) | Units) |
|
|
| 48MPD | 48MPE |
62L | 16,000 | 32,000 | 12,850 | 15,400 |
70M | 18,000 | 36,000 | 12,850 | 15,400 |
82N | 21,000 | 42,000 | 14,700 | 19,250 |
90P | 23,000 | 46,000 | 14,700 | 19,250 |
10R | 26,000 | 52,000 | 14,700 | 19,250 |
|
|
|
|
|
Controls Con®guration and Quick Test
SUPPLY FAN STATUS SWITCH (FS) Ð A snap acting single- pole,
The switch must be set prior to unit operation. To set the switch, turn the adjustment screw on top (center) of switch clockwise to increase set point, or counterclockwise to decrease set point. The set point switch range is 0.05 to
2.0in. wg with a deadband of 0.02 in. wg at minimum set point and 0.1 in. wg at maximum set point.
Set switch so that contact makes to NC when
CHECK FILTER SWITCH (CFS) Ð A snap acting SPDT switch is factory mounted in the auxiliary control box. The switch senses the differential pressure and provides the micro- processor module with a signal for ®lter status. Two lengths of plenum tubing connect the switch to probes located both upstream and downstream of the unit ®lters.
The switch must be set prior to unit operation. To set the switch, turn the adjustment screw on top (center) of switch slowly clockwise to ®nd the ``pivot'' point where the ®lter
status still reads clean under in the HSIO display. Check the switch operation with the
and nominal cfm delivery. See Table 22 for clean ®lter pres- sure drops for help in locating the ``pivot'' point. Once this point is found, turn the screw clockwise to obtain the set point at which the ®lter status will be dirty. Use Table 22 as a guide.
Table 22 Ð Filter Switch Dirty Set Point
| INCREASED |
| |
| PRESSURE DROP | APPROXIMATE | |
FILTER TYPE | TO ``DIRTY'' | CLOCKWISE | |
| FROM PIVOT | TURNS | |
| POINT |
| |
0.30 in. wg | 2 | ||
0.75 in. wg | 5 | ||
|
|
ENTHALPY CONTROL SET POINT Ð The enthalpy sen- sor (See Fig. 45) is located behind the ®lters in the right side economizer hood and is accessed through the ®lter access door. For maximum bene®t of outdoor air, set enthalpy sen- sor control to the A setting. At this setting, when the relative humidity is 50%, and the outdoor air is below 74 F, the sen- sor's relay contacts will be closed. See Fig. 46 and 47.
NOTE: Enthalpy control setting dial is on the enthalpy control.
Economizer Damper Linkage Adjustment Ð When replac- ing economizer damper motors, or if the linkage has come loose, it is critical that the linkages be adjusted correctly. They are sensitive, and incorrect adjustment can cause the motor to stall. Check linkage for free movement and com- plete range of travel.
Minimum Position Set Point Ð Minimum economizer po- sition is set using the keypad and display module. Refer to Control and Troubleshooting literature for more details.
ENTHALPY
SENSOR
Fig. 45 Ð Enthalpy Sensor
35