LIQUID TEMPERATURE AT LIQUID VALVE (DEG F)
150 |
|
125 | ADD CHARGE IF ABOVE CURVE |
| |
100 |
|
75 | REMOVE CHARGE IF BELOW CURVE |
| |
50 |
|
100 | 150 | 200 | 250 | 300 | 350 | 400 |
| LIQUID PRESSURE AT LIQUID VALVE (PSIG) |
|
|
ALL OUTDOOR FANS MUST BE OPERATING
Fig. 58 Ð Charging Chart Unit 48/50MP90P
LIQIUD TEMPERATURE AT LIQUID VALVE (DEG F)
150
130
110
90
70
50
100
TEMPERATURELIQUID | (DEGVALVELIQUIDAT F) | 150 |
|
125 |
| ||
ADD CHARGE IF ABOVE CURVE |
| ADD CHARGE IF ABOVE CURVE | |
|
|
| |
REMOVE CHARGE IF BELOW CURVE |
| 100 |
|
|
|
| |
|
| 75 | REMOVE CHARGE IF BELOW CURVE |
|
|
| |
|
| 50 |
|
150 | 200 | 250 | 300 | 350 | 400 | 450 |
|
|
|
|
|
|
| LIQUID PRESSURE AT LIQUID VALVE (PSIG) |
| 100 | 150 | 200 | 250 | 300 | 350 | 400 | |||
|
|
|
|
|
|
|
|
|
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
ALL OUTDOOR FANS MUST BE RUNNING
Fig. 59 Ð Charging Chart Ð Unit 48/50MP10R
Charging with Unit Off and Evacuated Ð Close liquid line service valve before charging. Weigh in charge shown in Table 1. Open liquid line service valve; start unit and allow it to run several minutes fully loaded. Check for a clear sight glass. Be sure clear condition is liquid and not vapor. Complete charging the unit.
Charging with Unit Running Ð If charge is to be added while unit is operating, it is necessary to have all condenser fans and compressors operating. It may be necessary to block con- denser coils at
Oil Charge (Refer to Table 3) Ð All units are fac- tory charged with oil. Acceptable oil level for each compres- sor is from 3¤8 to 1¤8 (on 06E299, 1¤8 max) of sight glass (see Fig. 44, page 29).
When additional oil or a complete charge is required, use only
Approved oils are:
Petroleum Specialties, Inc. Ð Cryol 150A (factory oil charge)
Texaco, Inc. | Ð Capella |
Witco Chemical Co. | Ð Suniso 3GS |
Do not reuse drained oil, and do not use any oil that has been exposed to atmosphere.
ADD OIL Ð Close suction shutoff valve and pump down crankcase to 2 psig (14 kPa).
IMPORTANT: For units with 2 compressors per re- frigeration circuit, both compressors must be running to adjust the oil level. Two oil level equalizer lines be- tween compressors distribute the oil to each compressor.
REMOVE OIL Ð Pump down compressor to 2 psig (14 kPag). Loosen the
NOTE: The crankcase will be slightly pressurized. Do not remove the plug, or the entire oil charge will be lost.
Small amounts of oil can be removed through the oil pump discharge connection while the compressor is running.
Moisture/Liquid Indicator Ð A clear ¯ow of liquid refrigerant indicates sufficient charge in the system. Bubbles indicate undercharged system or the presence of non- condensables. Moisture in the system measured in parts per million (ppm) changes the color of the indicator:
Green | Ð moisture below 45 ppm (dry) |
Chartreuse Ð 45 to 130 ppm (caution!) | |
Yellow | Ð moisture above 130 ppm (wet) |
Change ®lter driers at the ®rst sign of moisture in the sys- tem. See Carrier Charging Handbook for more information.
IMPORTANT: Unit must be in operation at least 12 hours before moisture indicator can give an accu- rate reading. With unit running, indicating element must be in contact with liquid refrigerant to give a true reading.
Filter Driers Ð The 48/50MP units use replaceable core type ®lter driers, one in each refrigeration circuit. The ®lter driers are located in the condenser sections, accessible from the right side of the unit.
49