Table 30 Ð Variable Frequency Drive (VFD) Display

Table 30 Ð Variable Frequency Drive (VFD) Display

DISPLAY

 

 

ACTION

Fref

Not used.

Fout

Displays the output frequency at which the VFD is cur-

rently operating. This is a display only function. The user

 

cannot change this displayed value.

lout

Displays the level of output current that the VFD is cur-

rently producing. This is a display only function. The user

 

cannot change this displayed value.

kWout

Displays the output power that the VFD is currently pro-

ducing. This is a display only function. The user cannot

 

change this displayed value.

F/R

Sets the rotation direction of the motor when a run com-

mand is given.

 

 

 

 

 

Montr

Press

ENTER

to access the monitor parameters

 

 

 

(U-01 through U-13).

 

Accel

Not used.

Decel

Not used.

Vmtr

Sets the rated voltage of the motor.

V/F

Sets a preset V/f pattern or allows a custom V/f pattern

to be set.

 

Fgain

Sets the frequency reference gain for the analog fre-

quency reference.

 

Fbias

Sets the frequency reference bias for the analog fre-

quency reference.

 

FLA

Sets the full load amps used for detecting motor over-

load. When FLA is set to 0 it is disabled.

 

PID

Enables or disables the PID.

kWsav

Enables or disables the energy saving function.

PRGM

Allows parameter programming.

 

 

 

 

LEGEND

PID Ð Proportional Integral Derivative

SERVICE

Service Access Ð All unit components can be reached through clearly labeled hinged access doors. These doors are equipped with tiebacks, but if heavy duty servicing is needed, it is recommended that the doors be removed or propped open.

Each door is held closed with 3 latches. The latches are secured to the unit with a single 1¤4-in. 220 x 1¤2-in. long bolt. See Fig. 50.

To open, loosen the latch bolt using a 7/16-in. wrench. Pivot the latch so it is not in contact with the door. Open the door. To shut, reverse the above procedure.

NOTE: Disassembly of the top cover may be required under special service circumstances. It is very important that the orientation and position of the top cover be marked on the unit prior to disassembly. This will allow proper replace- ment of the top cover onto the unit and prevent rainwater from leaking into the unit.

IMPORTANT: After servicing is completed, make sure door is closed and relatched properly, and that the latches are tight. Failure to do this can result in water leakage into the indoor-air section of the unit.

REMOTE Mode indication LEDs. The LEDs light when REMOTE Mode has been selected.

DISPLAY SECTION

Switch between Function LEDs*

Increase parameter number or displayed value.

Switch between LOCAL and REMOTE operation modes.

Run the motor. LED lights when drive is controlling motor speed.

 

 

REMOTE

 

 

SEQ

REF

Fref

Fout

lout

kWout

F/R

Montr

Accel

Decel

Vmtr

V / F

Fgain

Fbias

FLA

PID

kWsav

PGRM

DIGITAL OPERATOR

 

 

JVOP-131

 

 

 

DSPL

 

 

ENTER

LOCAL

 

 

 

REMOTE

 

 

 

RUN

STOP

RESET

 

 

*Pressing DSPL and ENTER keys simultaneously allows all parameter data to be read, but not set, while the drive is running.

Fig. 49 Ð VFD Digital Operator

4-digit, 7-segment LED display; shows selected operation status, fault code, or parameter data.

Function LEDs

KEYPAD SECTION

Displays data to be changed, and enters new data.*

Decrease parameter number or displayed value.

Stop the motor, or reset a drive fault. LED lights when drive is in stopped condition.

45