Carrier MPE62L-10R, 48MPD CL-3, Control Configuration, Keyboard, Display, Description, Entry

Models: MPE62L-10R 50MP62L-10R 48MPD

1 64
Download 64 pages 9.38 Kb
Page 63
Image 63
CONTROL CONFIGURATION

CONTROL CONFIGURATION

KEYBOARD

 

DISPLAY

 

 

DESCRIPTION

 

ENTRY

 

VALUES IN [ ] INDICATE FACTORY DEFAULTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOG ON

Enter password followed by

 

 

 

 

 

 

 

 

 

 

 

LOGGEDON

Logged on okay

 

 

 

 

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACT CFG

Factory con®guration

x

 

 

 

 

 

 

 

 

 

 

TYPE X

Unit type (0 = CV, 1 = VAV) [Default is 1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TYPE X

Verify unit type and change if necessary. If CV unit, see CV

 

 

 

 

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control con®guration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DTRS

Data Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable Data Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACT CFG

Factory Con®guration

 

 

 

 

 

 

 

 

 

 

 

LLAG X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use

 

to access lead/lag option Ð disable with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGBP (Item D, page CL-1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTER

 

 

DISABLE

Disable lead/lag (0 = DIS, 1 = ENB) [1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLD PRES

Con®gure building pressure control (modulating power

 

 

 

 

 

 

 

 

 

 

 

 

exhaust)

 

 

 

 

 

 

 

 

 

 

 

 

BPS .05

Use

 

for building pressure set point (range 0 to .5) [.05]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

BPS X

Set building pressure set point per job requirements

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGGEDON

Access log on/off function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOG OFF

Use

 

to access log off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGD OFF

Logged off okay

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

Run quick test to verify operation of unit functions

 

 

 

 

 

 

 

 

 

 

 

 

(see Controls and Troubleshooting Guide)

 

through

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETPOINT

Set system set points per job requirements

 

 

 

 

 

 

 

 

 

 

 

OHSP X

Set occupied heat set point (Range 55-80 F) [68] CV only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCSP X

Set occupied cool set point (Range 55-80 F) [78] CV only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UHSP X

Set unoccupied heat set point (Range 40-80 F) [55]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UCSP X

Set unoccupied cool set point (Range 75-95 F) [90]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPSP X

Set supply duct pressure set point (Range 0-5.0 in. wg) [1.5]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SASP X

Set supply air set point temperature (Range 45-70 F) [55]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIME

Current time/date

 

 

 

 

 

 

 

 

 

 

 

dow.hh.mm

Set day of week and time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm.dd.yy

Set month, day, and year

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DAYLIGHT

Set daylight savings time begin/end dates. Required if job

 

 

 

 

 

 

 

 

 

 

 

 

conditions require adjustment of clock for daylight savings time

 

 

 

 

 

 

 

 

 

 

 

 

(see Controls and Troubleshooting Guide)

 

 

 

 

 

 

 

 

 

 

 

HOLIDAY

Set holiday dates. Required if job conditions require a different

 

 

 

 

 

 

 

 

 

 

 

 

schedule on holidays than other days (see Controls and Trouble-

 

 

 

 

 

 

 

 

 

 

 

 

shooting Guide)

 

 

 

 

 

 

 

 

 

 

 

PERIOD X

Set occupied/unoccupied schedules. Required if job condi-

 

 

 

 

 

 

 

 

 

 

 

 

tions require unit to enter unoccupied cycle at programmed

 

through

 

 

times of day or days of week (see Controls and Troubleshoot-

 

 

 

ing Guide)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Data in brackets [ ] is default value.

 

 

 

 

CL-3