CONTROL | CONTROL POINT | |
CURVE | (Approx Deg F) | |
AT 50% RH | ||
|
A73
B68
C63
D58
Fig. 46 Ð Psychrometric Chart for
Enthalpy Control
NOTES:
1.Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy decrease.
2.When standard economizer is used with accessory differential enthalpy sen- sor, set enthalpy control to ``D'' setting.
Fig. 47 Ð Wiring Connections for Solid-State
Enthalpy Sensor (HH57AC077)
KEYPAD AND DISPLAY MODULE (HSIO) CONFIGURATION
IMPORTANT: The HSIO keypad and display module is required for initial
The keypad and display module provides unit function in- formation at the unit. See Fig. 48. The module consists of a keypad with 6 function keys, 5 operative keys, 10 numeric keys (0 through 9), and an alphanumeric
The HSIO keypad and display module is installed by con- necting the power and communication plugs and can be easily moved from one unit to another. Because of this ¯ex- ibility, one HSIO can be used for several units.
Unit operation is controlled by the status of the run/ standby mode on the HSIO. To access the mode, press
on the HSIO keypad, and then press | . |
The HSIO will display either STBY YES or STBY NO.
To enable the unit, press CLEAR or and press ENTER while
at the STBY YES display. To disable the unit, press
ENTER while at the STBY NO display. Clearing an alarm
that has stopped unit operation is accomplished by entering the STBY YES mode.
IMPORTANT: Use the STBY YES mode when ser- vicing the unit or running the quick test feature.
IMPORTANT: If remote start function is used, place LOCAL/REMOTE switch in Local (OFF) position when ever unit is placed in STBY YES.
SET UNIT TYPE Ð The correct unit type must be set. The default unit type is VAV. If the unit is being used in a VAV application, then the unit type does not need to be changed.
Table 23 Ð HSIO Keypad Key Usage
FUNCTION | USE | |||
KEYS | ||||
| ||||
|
|
| Status Ð To display diagnostic codes and | |
|
|
| current operating information about the unit. | |
|
|
| Quick Test Ð To check inputs and outputs for | |
|
|
| proper operation. | |
|
|
| History Ð To check most recent alarms. | |
|
|
|
| |
|
|
| Service Ð To enter speci®c unit con®guration | |
|
|
| information. | |
|
|
| Set Point Ð To enter operating set points and | |
|
|
| day/time information. | |
|
|
| Schedule Ð To enter occupied/unoccupied | |
|
|
| schedules for unit operation. | |
OPERATIVE | USE | |||
KEYS | ||||
| ||||
|
|
| Expand Display Ð To display a non- | |
|
|
| abbreviated expansion of the display. | |
|
|
| Clear Ð To clear the screen and return to previous | |
| CLEAR |
| display. Also used to enter data value | |
|
|
| of zero. | |
|
|
| ||
|
|
| Up Arrow Ð To return to previous display position. | |
|
|
| ||
|
|
|
| |
|
|
|
| |
|
|
| Down Arrow Ð To advance to next display position. | |
|
|
| ||
|
|
|
| |
|
|
|
| |
|
|
| To enter data. | |
| ENTER |
| ||
|
|
|
| |
|
|
|
|
STAT | EXPN | 1 | 2 | 3 | SRVC | TEST |
EDIT | ALRM | |||||
SET | SCHD | 4 | 5 | 6 | HIST | ALGO |
|
| 7 | 8 | 9 | CLEAR | |
|
| - | 0 |
| ENTER |
Fig. 48 Ð Keypad and Display Module (HSIO)
36