Cisco Systems Cisco ME 3400 manual Figure C-1 Stripping the Ground Wire

Models: Cisco ME 3400

1 88
Download 88 pages 28.6 Kb
Page 69
Image 69

Appendix C Connecting to DC Power

Grounding the Switch

Figure C-1 Stripping the Ground Wire

0.5 in. (12.7 mm) ± 0.02 in. (0.5 mm)

Insulation

Wire lead

60528

Step 3 Slide the open end of the ground lug over the exposed area of the 6-gauge wire.

Step 4 Using a Panduit crimping tool, crimp the ground lug to the 6-gauge wire.

Figure C-2 Crimping the Ground Lug

60529

Step 5 Use the two number-10-32 screws to attach the ground lug and wire assembly to the rear panel of the switch.

Step 6 Using a ratcheting torque screwdriver, torque each ground-lug screw to 15 lbf-in. (240 ounce-force inches [ozf-in.]). Figure C-3shows how to torque the ground screws on a Cisco ME DC switch.

Cisco ME 3400 Ethernet Access Switch Hardware Installation Guide

 

OL-7677-04

C-3

 