CONNECTING TO THE B32

WARNING: Improper installation may result in equipment damage or personal injury.

Always refer to the wiring diagrams that came with your controls before making electrical con- nections. The diagrams show the most accurate electrical component information.

Use shielded cable unless you run wires in metal conduit. Failure to use a metal shield will expose the controls to static electricity, which can damage electronic components.

When using shielded cable, make sure the shield is grounded inside the I/O stations only. It is also important to keep the communication wires away from conveying lines, which can produce large amounts of static electricity.

Each vacuum receiver, pump and

 

 

 

material valve in the system must be

 

 

 

wired to power or common/ground

Input/Output modules

terminals and Input/Output modules

 

 

 

 

 

 

inside the B32 control enclosure.

 

 

 

 

 

 

Each loader requires at least six

 

 

 

wire connections to the

 

 

 

Input/Output enclosure.

 

 

 

One additional wire is required for

each option or for a three-wire sensor used for either demand or loader full inputs. Connect the loader cable wires to the I/O station according to the color codes:

3-6

INSTALLATION

Basic 32 Loader Control

UGC007/0702