24
|Installation
Installing the EBM
NOTE: A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not
harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
To install the optional EBM:
1Plug the EBM cable into the UPS battery connector (see Figure 15).
Figure 15. EBM Installation with 5600W OL UPS (208V)
Installing the UPS
To install the UPS:
1If you plan to use Dell UPS Management Software, connect your computer to the USB port using
the supplied cable. For more information about communication options, see page 54.
2If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the
ground cable (not supplied) to the ground bonding screw. See “UPS Rear Panels” on page 15 for
the location of the ground bonding screw for each model.
3If an emergency power-off (disconnect) switch is required by local codes, see the following section,
“Installing Remote Emergency Power-off” (REPO) to install the REPO switch before powering on
the UPS.
4Plug the equipment to be protected into the UPS output receptacles, but do not turn on the
protected equipment.