Dell 5600R OL HV-US, K812N, 5600W manual Settings Description Available Settings Default Setting

Models: K812N 5600R OL HV-US 5600W

1 72
Download 72 pages 32.46 Kb
Page 44
Image 44

Table 7. Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]

Disabled

 

The UPS output is turned off in five minutes if the

 

 

UPS is on battery and output power is below the

 

 

selected level.

 

 

 

 

On Battery Notice Delay

[0s] [1s] [2s]...[99s]

0s

 

The UPS issues a “UPS on battery” notice in the

 

 

specified number of seconds after the UPS starts to

 

 

discharge the batteries.

 

 

 

 

Site Wiring Fault Alarm

[Enabled] [Disabled]

Disabled for 208V

 

 

 

models; Enabled for

 

 

 

all others

 

 

 

Bypass Voltage Low Limit

[-6%] [-7%]...[-20%] of nominal

-15% of nominal

 

The Bypass operation is disabled if the measured

 

 

bypass voltage level is below the nominal output

 

 

voltage (-15%).

 

 

NOTE: The Qualify Bypass setting may overrule the

 

 

Bypass Voltage Low Limit setting.

 

 

 

 

Bypass Voltage High Limit

[+6%] [+7%] [+20%] of nominal...

+10% of nominal

 

The Bypass operation is disabled if the measured

 

 

bypass voltage level is above the nominal output

 

 

voltage (+10%).

 

 

NOTE: The Qualify Bypass setting may overrule the

 

 

Bypass Voltage High Limit setting.

 

 

 

 

Qualify Bypass

[Always] [Never] [Bypass Disabled]

Always

 

If Always, Bypass operation is allowed when:

 

 

S

Bypass voltages > the value set for Bypass

 

 

 

Voltage Low Limit

 

 

S

Bypass voltages < the value set for Bypass

 

 

 

Voltage High Limit

 

 

S

Bypass frequency > (nominal frequency -3 Hz)

 

 

S

Bypass frequency < (nominal frequency +3 Hz)

 

 

S

Inverter is synchronized with Bypass when

 

 

 

unsynchronized transfers are disabled by the

 

 

 

value set for Unsynchronized Transfers

 

If Never, Bypass operation is always allowed; voltage and frequency limits are not in use.

If Bypass Disabled, Bypass operation is prohibited.

44 Operation

Page 44
Image 44