Dell 5600R OL HV-US, K812N, 5600W manual Troubleshooting

Models: K812N 5600R OL HV-US 5600W

1 72
Download 72 pages 32.46 Kb
Page 71
Image 71

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

 

 

 

 

Bypass AC Under Voltage

The measured voltage on

A notification alarm is generated and the

(Notice 4)

Bypass is less than the upper

notice is logged.

 

voltage limit specification for

 

 

Intermittent Alarm

Only apply this setting when Qualify Bypass is

bypass operation.

set to Always and utility is present, but below

 

 

 

 

 

the bypass undervoltage range.

 

 

 

Do not apply this setting if a Utility Not

 

 

Present alarm is active.

 

 

 

 

Bypass Under/Over Freq

The measured voltage on

A notification alarm is generated and the

(Notice 5)

Bypass is out-of-range for either

notice is logged.

 

the upper or lower voltage limit

 

 

Intermittent Alarm

Only apply this setting when Qualify Bypass is

specification for bypass

set to Always and utility is present, but outside

 

 

operation.

 

the bypass frequency range.

 

 

 

 

 

 

Do not apply this setting if a Utility Not

 

 

Present alarm is active.

 

 

 

 

 

Rectifier Input Over Current

The UPS has detected that

The UPS transfers to Battery mode if

 

(Alarm 26)

rectifier input current limits

supporting the load.

 

have been exceeded.

 

 

Continuous Alarm

 

 

 

 

 

 

 

 

 

Inverter Output Over

The UPS has detected that the

The UPS transfers to Bypass mode if

 

Current

inverter output current limits

supporting the load.

 

(Alarm 27)

have been exceeded.

 

 

 

 

 

Continuous Alarm

 

 

 

 

 

 

 

DC Link Over Voltage

The link or rail voltage has

The UPS transfers to Battery mode if

 

(Alarm 28)

exceeded its upper threshold

supporting the load.

 

limit.

 

 

Continuous Alarm

 

 

 

 

 

 

 

 

 

DC Link Under Voltage

The link or rail voltage has

The UPS transfers to Battery mode if

 

(Alarm 29)

dropped below its lower

supporting the load.

 

threshold limit.

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

DC Link Imbalance

The internal ± DC bus (DC

The UPS transfers to Battery mode if

 

(Alarm 1234)

rail) voltages generated in the

supporting the load.

 

UPS are imbalanced.

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

Rectifier Fault

The UPS has detected a fault in

Contact your service representative.

 

(Alarm 30)

the rectifier circuit while

 

 

attempting recovery from

 

 

Continuous Alarm

 

 

Bypass mode or Converter

 

 

 

 

 

 

mode.

 

 

 

 

 

 

 

 

Troubleshooting

71

Page 71
Image 71
Dell 5600R OL HV-US, K812N, 5600W manual Troubleshooting