Table 15. Battery

Configuration

5600W: (18) 216V, 7.2 Ah internal batteries; EBM (18) 216V, 9.0 Ah

 

 

Battery Type

CSB GP1272 7.2 Ah, YUASA NP7-12 7Ah, YUASA NPW 45-12 9.0 Ah

 

 

Voltage

5600W: 216 Vdc internal, 216 Vdc/30A EBM

 

 

Fuses

UPS: (2) 30A fuses

 

EBM: (2) 30A fuses

 

 

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

 

 

Charging

Approximately 4 hours to 90% usable capacity at nominal line and no

 

supplementary power supply load

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Battery Runtimes*

5600W internal batteries: 5.5 minutes at full load/17 minutes at half load

 

5600W with one EBM attached: 19 minutes at full load/45 minutes at half load

 

 

* Battery runtimes are approximate and vary depending on the load configuration and battery charge.

 

Bypass

 

 

Input

AC/DC

DC/AC

Output

Filter

Boost

Inverter

Filter

 

 

DC/DC

 

Charger

 

Battery

 

Figure 28. 5600W Online UPS Block Diagram

Specifications 65

Page 65
Image 65