Table 7. Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Set Date and Time

Set Month, Day, Year, Hours, Minutes, and Seconds

 

 

Date: mm/dd/yyyy

01/01/2009

 

Time: hh:mm:ss

12:00:00

 

NOTE: The date format is dependent on the

 

 

language selection.

 

NOTE: Time is a 24-hour clock.

Control Commands from Serial Port

[Enabled] [Disabled]

Enabled

If Enabled, control commands are accepted through the serial port, USB ports, or option card.

If Disabled, configuration and load control commands are restricted to LCD only.

Output Voltage

[Auto-sensing]

Auto-sensing

 

 

 

 

[200V] [208V]

 

 

 

 

 

[220V] [230V] [240V]

 

 

 

 

Output Frequency

[50Hz] [60Hz] [Auto-sensing]

Auto-sensing

 

 

 

Overload Alarm Level

[10%] [20%] [30%]...[100%]

100%

 

If 100%, the UPS issues an Output Overload alarm

 

 

at load > 100%.

 

 

NOTE: Output Overload Level 1 by default is set to

 

 

100% and is configurable from 10% to 100% in 10%

 

 

increments through the LCD setting menu. This

 

 

feature allows customers to be alerted before the

 

 

UPS has reached its rated capacity limits.

 

 

 

 

Automatic Start Delay

[Off] [0s] [1s] [2s]...[32767s]

LS1 0s

 

See “Configuring Load Segments” on page 49.

LS2 1s

 

 

 

Automatic on Battery Shutdown

[Off] [0s] [1s] [2s]...[32767s]

Off

 

See “Configuring Load Segments” on page 49.

 

 

 

 

Start on Battery

[Enabled] [Disabled]

Enabled

 

NOTE: Battery start is disabled from the factory and

 

 

remains disabled until the UPS has been powered

 

 

from utility and enters Standby mode. After the

 

 

UPS has been started once from utility, the Start on

 

 

Battery feature is automatically enabled. If this is set

 

 

by the user, it remains set.

 

 

 

 

Operation 43

Page 43
Image 43
Dell 5600W, K812N, 5600R OL HV-US manual Settings Description Available Settings Default Setting