Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Possible Cause

Action

Battery test did not run or was interrupted.

One of the conditions listed in

Resolve the condition, then restart the test.

“Running Automatic Battery

 

Tests” on page 53 was not

 

present.

 

The UPS does not transfer to Bypass mode.

The bypass utility does not qualify.

Check the bypass utility. The UPS is receiving bypass utility power that may be unstable or in brownout conditions.

Bypass mode is disabled.

Check that the Bypass settings are configured

 

correctly. See “Settings” on page 42.

UPS on Bypass

The UPS is operating from

(Notice 169)

Bypass mode.

 

Continuous Alarm

 

The equipment transferred to bypass utility power. Battery mode is not available and your equipment is not protected; however, the utility power continues to be passively filtered by the UPS. Check for one of the following alarms: overtemperature, overload, or UPS failure.

On Manual Bypass

UPS was manually commanded

None.

(Notice 143)

to transfer to Bypass mode and

 

will remain in bypass until

 

Intermittent Alarm

 

commanded.

 

 

 

 

 

 

 

 

Battery Disconnected

The UPS does not recognize the

If the condition persists, contact your service

(Alarm 199)

internal batteries.

representative.

 

 

Continuous Alarm

Battery voltage is lower than the

Verify that all batteries are properly connected.

batteries disconnected level

If the condition persists, contact your service

 

 

 

 

 

 

defined for this UPS. This may

representative.

 

 

 

be due to a blown fuse,

 

 

 

 

intermittent battery

 

 

 

 

connection, or battery cable

 

 

 

 

being disconnected.

 

 

 

 

Low Battery Warning

Battery time remaining or

This warning is approximate. The actual time to

(Alarm 56)

 

battery capacity is lower than

shutdown may vary depending on the UPS load

 

the battery low warning level

and presence of an External Battery Module

Continuous Alarm

defined for this UPS.

(EBM).

 

 

 

 

 

 

Shutdown Imminent

Communication to external

The alarm is issued when the battery time

(Alarm 55)

 

devices stops because the UPS

remaining reaches zero. All connected devices

 

has entered a state where it may

should have already shut down gracefully.

Continuous Alarm

abruptly stop operating without

 

 

 

 

 

 

 

 

further notice unless utility

 

 

 

 

returns.

 

 

 

 

 

 

68

Troubleshooting

 

 

Page 68
Image 68
Dell 5600R OL HV-US, K812N, 5600W manual Action