Table 14. Environmental and Safety
| 208V Models | 230V Models |
|
| |
Operating Temperature | Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F) | |
| Above 1,500 meters: 0°C to 35°C (32°F to 95°F) | |
|
| |
Transit/Storage | ||
Temperature |
|
|
|
| |
Relative Humidity | ||
|
| |
Operating Altitude | Up to 3,048 meters | |
|
| |
Audible Noise | Less than 55 dBA on line/bypass mode (less than 75% load), room temperature | |
|
| |
Fan Speed | Off when the UPS is in Standby mode or there is no load | |
| Low speed: when the load is <80% | |
| High speed when the load is >80% or the UPS is in Battery mode | |
|
| |
Surge Suppression | ANSI/IEEE C62.41; 1991 Category B3 | |
|
|
|
Safety Conformance | UL 1778 4th Edition; | UL 1778 4th Edition; CSA C22.2, |
| CSA C22.2, No. 107.3 | No. 107.3; IEC/EN |
|
| IEC/EN |
|
|
|
Safety Markings | UL, cUL, VCCI | UL, cUL, CE, GS, GOST, BSMI, |
|
| |
|
|
|
EMC (Class A) | FCC Part 15, | IEC/EN |
|
| |
|
| AS/NZS 62040.2; |
FCC Part 15; KN22; GB7260.2;
EN 55024/CISPR 24
64 Specifications