Ethernet Communication Module DVPEN01-SL
4.Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete the setting.
5.After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to the MPU. See below for the program design:
X0 | | | | |
T0 | K100 | K3 | K1 | K1 |
X0 | | | | |
T0 | K100 | K4 | K1 | K1 |
Y0 | | | | |
T0 | K100 | K5 | K1 | K1 |
Y0 | | | | |
T0 | K100 | K6 | K1 | K1 |
END | | | | |
Explanations: | | | | |
•If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of DVPEN01-SL, and the first E-Mail will be sent out.
•If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of DVPEN01-SL, and the second E-Mail will be sent out.
•If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of DVPEN01-SL, and the third E-Mail will be sent out.
•If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of DVPEN01-SL, and the fourth E-Mail will be sent out.
6.8Application of Data Exchange (1)
Application
Network requirement
Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A
(1)Adopting static IP.
(2)IP of PLC_A: 192.168.0.4
(3)IP of PLC_B: 192.168.0.5”
(4)Update from PLC_B to PLC_A
DVP-PLC Operation Manual | 45 |