Ethernet Communication Module DVPEN01-SL

4.Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete the setting.

5.After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to the MPU. See below for the program design:

X0

 

 

 

 

T0

K100

K3

K1

K1

X0

 

 

 

 

T0

K100

K4

K1

K1

Y0

 

 

 

 

T0

K100

K5

K1

K1

Y0

 

 

 

 

T0

K100

K6

K1

K1

END

 

 

 

 

Explanations:

 

 

 

 

If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of DVPEN01-SL, and the first E-Mail will be sent out.

If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of DVPEN01-SL, and the second E-Mail will be sent out.

If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of DVPEN01-SL, and the third E-Mail will be sent out.

If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of DVPEN01-SL, and the fourth E-Mail will be sent out.

6.8Application of Data Exchange (1)

Application

Network requirement

Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A

(1)Adopting static IP.

(2)IP of PLC_A: 192.168.0.4

(3)IP of PLC_B: 192.168.0.5”

(4)Update from PLC_B to PLC_A