Ethernet Communication Module DVPEN01-SL

6.12 Application of Data Exchange (5)

Application

Network requirement

Writing the time in RTC in PLC_B directly into D0 ~ D6 of PLC_A without writing in ladder diagram into PLC_A.

(1)Adopting static IP.

(2)IP of PLC_A: 192.168.0.4

(3)IP of PLC_B: 192.168.0.5

(4)Update from PLC_B to PLC_A.

1.See 6.1 for how to set up communication.

2.Compile the ladder diagram in the MPU and download it to PLC_B. We do not need to write any corresponding ladder diagram into PLC_A.

M1000

M1013 M2 M1

M1

M2

= D14 K2

= D14 K3

TRD

D100

 

 

 

SET

M1

 

 

 

TOP

K100

K28

K0

K1

TOP

K100

K26

HC0A8

K1

TOP

K100

K25

H4

K1

TOP

K100

K81

H1000

K1

TOP

K100

K84

H1000

K1

TOP

K100

K85

K7

K1

TOP

K100

K86

H1064

K1

TOP

K100

K14

K0

K1

TOP

K100

K13

K1

K1

SET

M2

 

 

 

RST

M1

 

 

 

FROM

K100

K14

D14

K1

RST M2

RST M2

END

Explanations:

The data exchange will be executed every one second.