Ethernet Communication Module DVPEN01-SL

1.See 6.1 for how to set up the communication.

2.Use DCISoft for RTU-EN01 to set up the mapping CR for read/write.

3.Use DCISoft for DVPEN01-SL to set up the mapping start address and number of data. RX: M2000 ~

M2009, RY: M3000 ~ M3009, RCR Read: D2000 ~ D20009, RCR Write: D3000 ~ D3009

4.Edit the ladder diagram in the MPU and download it to DVPEN01-SL. See the program design as shown below:

DVP-PLC Operation Manual

55