Ethernet Communication Module DVPEN01-SL

M1000

 

 

TRD

D100

 

 

 

 

 

 

 

 

 

M1013

M2

M1

SET

M1

 

 

 

 

 

 

 

 

 

M1

 

 

TOP

K100

K28

K0

K1

 

 

 

 

 

 

TOP

K100

K26

HC0A8

K1

 

 

 

TOP

K100

K25

H4

K1

 

 

 

TOP

K100

K29

D100

K7

 

 

 

TOP

K100

K14

K0

K1

 

 

 

TOP

K100

K13

K1

K1

 

 

 

SET

M2

 

 

 

 

 

 

RST

M1

 

 

 

M2

 

 

 

 

 

 

 

 

 

 

FROM

K100

K14

D14

K1

 

= D14 K2

RST

M2

 

 

 

 

= D14 K3

RST

M2

 

 

 

 

 

 

END

 

 

 

 

Explanations:

 

 

 

 

 

 

The data exchange will be executed every one second.

Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination PLC.

Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 = H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

Write the data in RTC into CR#29 ~ CR#35.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

2.Compile the ladder diagram for PLC_A and download it to PLC_A.

M1013

 

 

 

 

FROM

K100

K49

D0

K7

END

 

 

 

 

Explanations:

 

 

 

 

The received data are stored in CR#49 ~ CR#55.

The data received every one second are written into D0 ~ D6.

DVP-PLC Operation Manual

51