Venting Installation instructions
Continued
SNORKEL TERMINATION INSTALLATION Recommended Applications Models (V)CD36R and (V)CD36T:
•Installations requiring vertical rise on building exterior.
•Installation using snorkel termination to achieve 1 ft. above grade.
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the build- ing. If installing snorkel below grade
you must provide proper drainage to prevent water from entering snorkel (see Figure 23, page 15). Do not back fill around snorkel termination.
Snorkel |
Termination |
12" |
Min. |
|
| Snorkel |
Snorkel | Wall | Termination |
Termination |
| |
Firestop |
| |
|
| |
| 90° Elbow |
|
|
| 12" Min. |
12" Min. |
|
|
Adequate |
|
|
Drainage |
|
|
Figure 23 - Snorkel Termination Configuration For Below Ground Installation
HORIZONTAL VENT INSTALLATIONS
USING MULTIPLE 90° ELBOWS (V)CD36T
TOP VENT
The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.
90° Elbow
Venting with Two 90° Elbows
| Horizontal (H)+ |
Vertical (V) | Horizontal (H2) |
7' Min. | 10' Max |
8' Min. | 12' Max |
9' Min. | 14' Max |
10' Min. | 16' Max |
11' Min. | 18' Max |
13' Min. | 20' Max |
90° Elbow
Figure 24 - Horizontal Termination Configuration For Venting Using Two 90° Elbows
(Model (V)CD36T)
www.desatech.com | 15 |