Dialogic® SS7G21 and SS7G22 Signaling Servers Hardware Manual Issue 7

Figure 15. DC Power Terminal Lug

When selecting an appropriately sized power wire, consider the power rating of the product, and the length of the cable run. When installing the product in locations other than telecommunications centres, ensure that the cables connecting the DC power input, and the safety ground conductor, are less than 3 metres in length.

When selecting a suitable DC power source for connection to, ensure that it complies with the WARNING – IF DC POWER SUPPLIES ARE INSTALLED warning in Chapter 7, “Warnings and Cautions”. This covers the following aspects; isolation, installation in a restricted-access location, main DC power disconnect, grounding the rack installation, and overcurrent protection.

9.2.3DC Power Supply Module, Transferring Connections

When replacing a DC Power Supply Module, the terminal block, with wires attached, can be removed from the faulty Power Supply Module and assembled to the replacement Power Supply Module as follows:

1.Remove the two screws that secure the terminal block to the Power Supply Module and pull the terminal block away from the module. See Figure 13 on page 52.

Note: Removing the two screws also frees the terminal block cover, but it can be retained by attaching it to the removed terminal block.

2.Remove the faulty Power Supply Module from the chassis.

3.Install the replacement Power Supply Module. See Section 9.2.5, “Replacing a DC Power Supply Module” on page 53.

4.On the newly installed Power Supply Module, lift the insulating cover on the terminal block to access the two screws that secure the terminal block to the chassis.

5.Remove the two screws and carefully pull the terminal block away from the Power Supply Module.

6.Align the old terminal block (with wires attached) with the terminal block receptacle on the new Power Supply Module and carefully push the terminal block into the Power Supply Module.

7.Secure the terminal block in position using the two securing screws. See Figure 13 on page 52.

8.Close and latch the insulating cover so that it covers the terminals.

9.2.4AC-input Power Supply Cage, Connection

Two AC power input connectors, type IEC320, are provided at the rear of the Power Supply Cage of AC powered product. Connection to an AC power outlet is covered in Part I, Section 6.3, “AC Power Input” on page 35 (it is not essential for it to be performed by a qualified service technician).

9.2.5Replacing a DC Power Supply Module Observe the following cautions:

53

Page 53
Image 53
Dialogic SS7G22, SS7G21 manual DC Power Supply Module, Transferring Connections, AC-input Power Supply Cage, Connection