Dialogic® SS7G21 and SS7G22 Signaling Servers Hardware Manual Issue 7
WARNING
IF DC POWER SUPPLIES ARE INSTALLED:
ISOLATION:
The product with DC input is to be installed in a Restricted Access Location in accordance with articles
MAIN DC POWER DISCONNECT:
You are responsible for installing a properly rated DC power disconnect for the entire rack unit. This DC power disconnect must be readily accessible, and it must be labelled as controlling power to the entire rack unit, not just to this product.
GROUNDING THE RACK INSTALLATION:
To avoid the potential for an electrical shock hazard, you must reliably connect a safety ground conductor to the product. The safety ground conductor must be a minimum 14AWG connected to the safety ground studs on the rear of the product, with a closed
OVERCURRENT PROTECTION:
Overcurrent protection circuit breakers must be provided as part of each host equipment rack and must be installed between the DC source and this product. The branch circuit protection shall be rated minimum 75 VDC, 10 Amps maximum per feed pair. If the DC power system for the equipment rack is installed with more than 10 Amps of protection, you must provide supplemental protection for this product. The overall current rating of this product configured with two power supplies is less than 4 Amps.
9