Model |
| Weight kg | |
Shipping |
| Installed | |
|
| ||
Powerware | 1610 |
| 1430 |
Powerware | 1610 |
| 1430 |
|
|
|
|
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet and outlets are in the top.You must allow clearance in front of and above each cabinet for proper air circulation.The clearances required around the UPS cabinet are shown inTable
From top of cabinet | Minimum clearance over the UPS cabinet is 458 mm for ventilation |
From front of cabinet | 915 mm working space |
From back of cabinet | None required |
From right side of cabinet | None required, but for easier service 500 mm is recommended. |
From left side of cabinet | None required |
Table |
|
The basic environmental requirements for operation of the UPS system are:
•AmbientTemperature Range:
•Recommended Operating Range:
•Maximum Relative Humidity: 95%, noncondensing
The UPS ventilation requirements are shown inTable
Rating/kVA | Input/output voltage | Heat rejection |
|
| BTU/hr x 1000/hr |
2*275 kVA | 400/400 | 88.7 |
550 kVA | 400/400 | 88.7 |
|
|
|
Table
Ventilation required for cooling air exhaust: approximately 1410
1027574 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 11 |
Revision B | User’s and Installation Guide |
|