10 Product specifications
10.1 Model numbers
The UPS systems are housed in
Models | Power Rating | Frequency |
Powerware | 450 kVA | 50/60 Hz |
Powerware | 550 kVA | 50/60 Hz |
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2 Single module specifications
10.2.1 UPS system inputOperating Input Voltage | 400 Vac for operation from 340 Vac to 460 Vac | |
(Nominal + | ||
| ||
Operating Input Frequency Range | ±5 Hz | |
Operating Input Current | See Table | |
Reduced for Generator Adjustable | ||
| ||
Input Current Harmonic Content | 5% THD at full load | |
Power Factor | Minimum 0.98 | |
Line Surges | 6 kV OC, 3 kA SC per ANSI 62.41 and IEC | |
Battery Voltage | 480 Vdc |
UPS Output Capacity | 100% rated current | |
Output Voltage Regulation | ±1% (10% to 100% load) | |
| 380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac | |
Output Voltage Adjustment (Nominal | 400 Vac nominal, adjustable from 388 Vac to 412 Vac | |
| 415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac | |
Output Voltage Harmonic Content | 1.5% max THD (linear load) | |
5% max THD (nonlinear load) | ||
| ||
Output Current | See Table | |
Output Voltage Balance | 3% for 100% maximum load imbalance (linear load) | |
Output Voltage Phase Displacement | 3° for 100% maximum load imbalance (linear load) | |
Output Transients | ±5% for 100% load step or removal | |
Frequency Regulation | ±0.1 Hz free running | |
Synchronous to Bypass | Bypass within voltage limits of +5%, | |
bypass within ±3 Hz | ||
| ||
Frequency Slew Rate | 1 Hz per second maximum | |
| 110% for 10 minutes | |
Overload Capability | 125% for 30 seconds | |
| 150% for 10 seconds | |
Max battery charging current | 120 A |
1027574 | UPS 450 - 550 kVA (2x225 - 2x275 kVA) | 74 |
Revision B | User’s and Installation Guide |
|