To install wiring to connections:
1.Verify the UPS system is turned off and all power sources are removed. See Chapter 5, “UPS Operating Instructions,” for shutdown instructions.
2.If not already accomplished, remove one top screw and two bottom screws securing the UPS left front panel (see Figure
3.Remove one top screw and two bottom screws securing the UPS center front panel (see Figure
4.Terminal blockTB3 is accessible on the left side of the
5.Remove the UPS cabinet top interface entry plates to drill or punch holes (see Figure
6.Reinstall the entry plates.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required.
7.To locate the appropriate terminals and review the wiring and termination requirements, see paragraph 2.2.2 on page 14,Table
8.Route and connect the wiring.
9.If wiringTB1 battery interface connections, proceed to paragraph 3.5.2; if wiring the
10.When all wiring is complete, reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
11.Reinstall the left and center front panels removed in previous steps and secure with the retained hardware.
NOTE Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28 Vdc.
NOTE Alarm relay
NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of .75 mm2.